Appendix D • Liquid Injection Valve Setup Instructions and Quick Start Guide
Danfoss ICM/ICAD Valve Setup Instructions
The following items need to be setup in order for the valve to operate properly.
1.
Press the "Circle" button on the valve. A value of "01" should be shown on the screen.
2.
Press the "Circle" button. There should be a value of "1" shown. If not use the up/down arrows to change it to
the correct value. Press the "Circle" button when done.
3.
Press the "Up" arrow button. A value of"02" should be shown on the screen.
4.
Press the "Circle" button. There should be a value of "1" shown. If not use the up/down arrow buttons to change
it to the correct value. Press the "Circle" button when done.
5.
Press the "Up" arrow button. A value of "03" should be shown on the screen.
6.
Press the "Circle" button. There should be a value of "2" shown. If not, use the up/down arrow buttons to change
it to the correct value. Press the "Circle" button when done.
7.
Press the "Up" arrow button until a value of "04" is shown on the screen.
8.
Press the "Circle" button. There should be a value of "50" shown. If not, use the up/down arrow buttons to
change it to the correct value. Press the "Circle" button when done.
9.
Press the "Up" arrow button until a value of "07" is shown on the screen.
10. Press the "Circle" button. There should be a value of "1" shown. If not, use the up/down arrow buttons to change
it to the correct value. Press the "Circle" button when done.
11. Press the "Up" arrow button until a value of "10" is shown on the screen.
12. Press the "Circle" button. Press the up/down arrow button to change the value to "11". Press the "Circle" button.
13. Press the "Up" arrow button until a value of "26" is shown on the screen.
14. Press the "Circle" button. Press the up/down arrow buttons to change the value to the correct valve that is on the
unit. The value number is listed on the valve. The values and valves are as follows:
0: No valve selected. Alarm A1 will become active.
1: ICM20 with ICAD 600
2: ICM25 with ICAD 600
3: ICM32 with ICAD 600
4: ICM40 with ICAD 900
5: ICM50 with ICAD 900
6: ICM65 with ICAD 900
15. Press the "Circle" button.
The valve is now ready to be used.
D − 2
VSS/VSM/VSH/VSSH • Installation, Operation and Maintenance Manual • Emerson • 35391SD