Software
The MS-E10 device ships with Niagara 4.7 and the drivers for BACnet, Modbus and SNMP. Note that it is the recommended
security best practice to update to the latest software release.
Default platform daemon credentials
MS-E10 devices are shipped with default platform daemon (administrator) username and password credentials. The default
credentials are:
• Username: tridium
• Password: niagara
Initially, you use the factory default credentials to open (login) a platform connection to the MS-E10 device. Default credentials
are temporary. During your startup commissioning, you must replace the default platform admin account with at least one
different platform admin user.
Note:
For security reasons, be sure to guard the credentials for such platform users closely.
Default system passphrase
In addition to the default platform daemon (administrator) credentials, MS-E10 devices are shipped with a default system
passphrase. The default passphrase is:
• Passphrase: niagara
Default station details
The E10 device also ships with a default NiagaraStation pre-installed. By default, the network configuration for the station is set
to the daisy chain mode. The default station name is a combination of the controller model and the unique hostid. For example,
Edge10_3F88_5ACB_C28A.
The default station includes the EdgeIoNetwork already installed to access the physical I/Os. The default station credentials are:
• Username: admin
• Password: Admin12345
Note:
You are required to enter new credentials on the initial login.

Initial IP address

Previous controllers shipped with a static IP address. To facilitate bulk deployment, MS-E10 devices are shipped with a one-time
feature enabled that allows the controller to initially attempt to connect to a DHCP server.
Upon first startup, when IP connectivity is detected, the MS-E10 initially requests an IP address via DHCP. If a DHCP address is
not found, the controller reverts to a static IP address based on its serial number. See the following section for examples.
This feature only applies during the first power up cycle with an active Ethernet connection. At all other times the network
settings are set or modified the same as on the JACE-8000.
Note that for this onetime feature to execute, there must be an active Ethernet connection. A flag is maintained that enables this
feature. This feature will execute once and then the flag will be disabled.
During a factory restore the flag enabling this is reset to enabled.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
MS- E10 User Guide
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pbase10

Table of Contents