Figure 37: Accessing ipchanges.bog in open platform connection
Recovering factory defaults
The process of recovering factory defaults returns the MS-E10 device to the state it was in when it shipped from the factory. This
procedure describes the steps to recover factory defaults when using a terminal emulator program to access the device's system
shell menu.
Prerequisites:
A USB-to-micro USB cable (same cable as that used to connect a smart phone to a computer) connecting the
•
controller to your PC. The Debug port on a controller is a standard Micro-A type USB port used to access the serial
shell.
A terminal emulator (system shell program), such as PuTTY, installed on your PC.
•
Note:
Recovering factory defaults removes all platform and station data in the device. Be sure to back- up data prior to performing this
procedure.
Following are a couple of scenarios for which you might choose to recover factory defaults:
While commissioning a brand new MS-E10 device, you make an error entering the default platform daemon credentials
•
or passphrase. The result is that you cannot commission the controller. In this scenario, your only option is to recover
the factory defaults.
When decommissioning the MS-E10 device, a best practice to follow is recovering the factory defaults in order to wipe
•
all of the platform and station data in the controller.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
MS- E10 User Guide
62