Recovering Factory Defaults - LG niagara4 MultiSITE Edge 10 User Manual

Table of Contents

Advertisement

Figure 37: Accessing ipchanges.bog in open platform connection

Recovering factory defaults

The process of recovering factory defaults returns the MS-E10 device to the state it was in when it shipped from the factory. This
procedure describes the steps to recover factory defaults when using a terminal emulator program to access the device's system
shell menu.
Prerequisites:
A USB-to-micro USB cable (same cable as that used to connect a smart phone to a computer) connecting the
controller to your PC. The Debug port on a controller is a standard Micro-A type USB port used to access the serial
shell.
A terminal emulator (system shell program), such as PuTTY, installed on your PC.
Note:
Recovering factory defaults removes all platform and station data in the device. Be sure to back- up data prior to performing this
procedure.
Following are a couple of scenarios for which you might choose to recover factory defaults:
While commissioning a brand new MS-E10 device, you make an error entering the default platform daemon credentials
or passphrase. The result is that you cannot commission the controller. In this scenario, your only option is to recover
the factory defaults.
When decommissioning the MS-E10 device, a best practice to follow is recovering the factory defaults in order to wipe
all of the platform and station data in the controller.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
MS- E10 User Guide
62