Bicker Elektronik UPSI-IP-1 Series User Manual

Bicker Elektronik UPSI-IP-1 Series User Manual

Hide thumbs Also See for UPSI-IP-1 Series:

Advertisement

Quick Links

English
User Manual UPSI-IP-1 Series
UPS SYSTEM
IP65 / 67
Bicker Elektronik GmbH
Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPSI-IP-1 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Bicker Elektronik UPSI-IP-1 Series

  • Page 1 English User Manual UPSI-IP-1 Series UPS SYSTEM IP65 / 67 Bicker Elektronik GmbH Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany...
  • Page 2 UPSI-IP-1 Series Legend of used symbols Symbol Description Attention! Important hazard warning. Do not dispose of in the domestic waste. Warning of electrical voltage. Revision Directory Date Change 16.04.2021 Initial version Revision 0-1 26.05.2021 Release version Revision 1 Revision 1...
  • Page 3 UPSI-IP-1 Series LiFePO4 INSIDE Revision 1...
  • Page 4: A Brief Specification Upsi-1208Ip-11U / Upsi-2406Ip-12U

    100 % (at +25° C ) Dimensions W / H / D 140 x 140 x 90 mm ±0.5 mm (without connectors and mounting brackets) Housing size 1 (UPSI-IP-1 series) Weight 1.84 kg 1.92 kg Input and output cable 3x 2.5 mm (incl.
  • Page 5 UPSI-IP-1 Series Backup time* UPSI-1208IP-11U Backup time BP-LFP-1025 Backup time* UPSI-2406IP-12U Backup time BP-LFP-1325 *Backup time depends on battery capacitance, load and temperature. At very high or low temperatures a reduction of backup time occurs. Unless otherwise specified, the values apply to measurements at +25 °C...
  • Page 6: Table Of Contents

    UPSI-IP-1 Series Brief specification UPSI-1208IP-11U / UPSI-2406IP-12U ........4 Introduction and description ................7 B1 Description of the product and its functions ....................7 B2 Intended use – devices ............................8 B3 Intended use – connecting cables ........................8 Safety instructions ....................9 Technical Data .....................
  • Page 7: B Introduction And Description

    UPSI-IP-1 Series B Introduction and description Read carefully before initial operation! This manual shall help the user to get familiar with the product and its components and features. It shall pro- vide information as accurately and completely as possible. The manual as well as all documents has to be read and followed strictly before installation. Otherwise in cer- tain situations warranty and guarantee can be cancelled partly or completely.
  • Page 8: B2 Intended Use - Devices

    UPSI-IP-1 Series B2 Intended use – devices These devices are primarily designed for use under difficult and extreme environmental conditions and can be used both indoors and outdoors. They have been developed for professional use in areas such as industrial control, communication and measurement technology.
  • Page 9: C Safety Instructions

    UPSI-IP-1 Series C Safety instructions WARNING! Disregarding of following issues can result in electric shock, fire, serious injury or death. 1. Care must be taken to ensure proper and professional wiring. 2. The device pack must not be exposed to fire and temperatures outside the specification.
  • Page 10: D Technical Data

    UPSI-IP-1 Series D Technical Data D1 General Technical Data INPUT DATA Unless otherwise stated, all specifications apply to 25° C ambient temperature, 12 or 24 V DC input voltage and nominal output current (I UPSI-1208IP-11U UPSI-2406IP-12U Input voltage 12 V DC...
  • Page 11 UPSI-IP-1 Series OUTPUT DATA – NORMAL MODE Unless otherwise stated, all specifications apply to 25° C ambient temperature, 12 or 24 V DC input voltage and nominal output current (I UPSI-1208IP-11U UPSI-2406IP-12U Output voltage 12 V DC 24 V DC Output voltage range –...
  • Page 12 UPSI-IP-1 Series OUTPUT DATA – BATTERY MODE Unless otherwise stated, all specifications apply to 25° C ambient temperature, 12 or 24 V DC input voltage and nominal output current (I UPSI-1208IP-11U UPSI-2406IP-12U Output voltage 12 V DC 23.5 V DC Output voltage range n.
  • Page 13 UPSI-IP-1 Series ENERGY STORAGE UPSI-1208IP-11U Installed type BP-LFP-1025 Battery technology LiFePO4 Charging method CC / CV / CP Nominal voltage U 9.6 V End-of-charge voltage 10.4 V Charging current 4.5 A max. Undervoltage protection 6.6 V Nominal capacity 2.5 Ah (25 Wh)
  • Page 14 UPSI-IP-1 Series CONNECTION DATA INPUT / OUTPUT (HOUSING) Connector Input Output Connector type Flange plug Flange socket Design Pin (male), straight Socket (female), straight Connection locking Central screw Chassis-internal contact type: Screw clamp type Stranded wire to connectors Mechanical service lifetime >500 plug cycles...
  • Page 15 UPSI-IP-1 Series CONNECTION DATA – USB (HOUSING) Connector type Flange socket Design Socket (female), straight Anschluss-Verriegelung Snap Chassis-internal contact type: Solder Stranded wire to connectors Mechanical service lifetime >500 plug cycles Stranded wire size and cross section 5x AWG24 (ca. 0.25 mm²) internal CONNECTION DATA –...
  • Page 16 UPSI-IP-1 Series DATA INTERFACE – USB Transmission physics USB 2.0 Topology Point-to-point Protocol VCOM, HID Transmission length ≤3 m Access time <1 s Chipset Electrical isolation GENERAL DATA Flammability class according to UL 94 Weight UPSI-1208IP-11U: 1.84 kg, UPSI-2406IP-12U: 1.92 kg...
  • Page 17 UPSI-IP-1 Series ENVIRONMENTAL CONDITIONS Ambient temperature (operation) –20…+50 °C Ambient temperature (start up without load) –20 °C Ambient temperature –30…+55 °C (storage / transport) Max. permitted humidity 100 % (at +25 °C) Operating altitude ≤4000 m Climate class 3K24 (EN 60721-3-3:2020-5)
  • Page 18 UPSI-IP-1 Series INTERFERENCE IMMUNITY ACCORDING TO EN 61000 (INDUSTRY) Basic standard CE Fulfilled requirements according to EN 61000 (CE) (Interference immunity of industrial environment) Electrostatic discharge EN 61000-4-2 Contact discharge 4 kV Air discharge 8 kV Comment Criterion B Electromagnetic HF field...
  • Page 19 UPSI-IP-1 Series EMISSION ACCORDING TO EN 55016-2-3 (DOMESTIC) Basic standard CE Fulfilled requirements according to EN 55016-2-3 (CE) (Domestic) Conducted emission from the power port EN 55016-2-3 Frequency range 150 kHz–30 MHz Comment Conform Electric field radiated emission EN 55016-2-3 Frequency range 30 MHz–1 GHz...
  • Page 20: D2 Drawing Upsi-1208Ip-11U / Upsi-2406Ip-12U

    Tolerance ±0.5 mm 120mm 136mm 140mm E Name / Address / Support E-Mail / Phone number of the manufacturer Bicker Elektronik GmbH · Ludwig-Auer-Straße 23 · 86609 Donauwörth · Germany E-Mail: support@bicker.de · Tel.: +49 (0) 906 70595-0 Revision 1...
  • Page 21: F General Data

    UPSI-IP-1 Series F General Data F1 Assembly and installation advice Installation and operation of this device is only allowed to be executed by a qualified electrician! The application has to be separated from any power during the mounting process. The connector cables have to be correctly locked with the device connections and may only be screwed hand-tight (max.
  • Page 22: F3 Description Of Connectors

    UPSI-IP-1 Series F3 Description of connectors INPUT FUNCTION Vin + Vin – (GND) OUTPUT FUNCTION Vout + Vout – (GND) FUNCTION Data – V– (GND) Shield Data+ (GND) Revision 1...
  • Page 23: F4 Dimensioning The Upstream Power Supply

    UPSI-IP-1 Series F4 Dimensioning the upstream power supply Ensure that the upstream power supply is correctly dimensioned to guarantee the charging process of the batteries and the correct functioning of the application. For charging the energy storage even at higher load must be taken care of.
  • Page 24: F5 Connecting Diagram

    UPSI-IP-1 Series F5 Connecting diagram – (2) – (2) APPLICATION (V + (1) + (1) CONNECTING ORDER 1. APPLICATION (V 2. DC SOURCE (V 3. USB Dismantling order reverse to connection! – ATTENTION! 1. Note polarity! 2. Pay attention to the maximum cable length. The supplied cables should not be lengthened because if the cables are too long, an unintentional power fail may be triggered (e.g.
  • Page 25 UPSI-IP-1 Series  WIRING DIAGRAM 12V or 24 V 12 V or 24 V APPLICATION INPUT SOURCE IN TOTAL LOAD BATTERY PINOUT OF POWER CABLES BATTERY UPSI 1 = V+ 2 = V–  DO NOT ! DC INPUT SOURCE...
  • Page 26: F6 Initial Operation

    UPSI-IP-1 Series F6 Initial operation The correct installation of the UPS has to be ensured. The start is accomplished by connecting the upstream power supply: When a voltage higher than 11.5 or 22.5 V is connected to the input terminals, the energy storage gets queried and transmits its data. The UPS sets the corresponding end-of-charge voltage and releases the pack.
  • Page 27: F7 Overview Connector / Counterpart With Description / Scope Of Delivery

    UPSI-IP-1 Series F7 Overview connector / Counterpart with description / Scope of delivery CONNECTOR PART NO. HOUSING END PART NO. CABLE END Binder 09422315004 Binder 9902100004 Binder 09422415004 Binder 9902090004 Binder 9991160005 Binder 9991130005 SCOPE OF DELIVERY QUANTITY DESCRIPTION 1x device UPSI-1208IP-11U bzw.
  • Page 28: F8 Charging Time

    UPSI-IP-1 Series F8 Charging time Charging times depend on energy storage, input voltage and the load current. F9 Reverse polarity / Overcurrent / Short circuit Reverse polarity: The device has active reverse polarity protection at the input if the input strands are connected with reverse polarity while the device is still switched off (e.g.
  • Page 29: F12 Status Led

    UPSI-IP-1 Series F12 Status LED Valid from firmware version 2.1.19 MAIN STATES Always on Status: mains voltage >> Mains voltage is present. 1 Hz flash Status: Battery mode (1 s on, 1 s off) >> Mains voltage is not present.
  • Page 30: F13 Shutdown Diagram

    UPSI-IP-1 Series F13 Shutdown diagram False Power Fail True Ignition-Timer True Enabled False Shutdown SOC Max. Backup Shutdown-Timer Ignition Pin False Enabled Enabled OS Enabled High True True True True False False Shutdown SOC Max. Backup Shutdown-Timer Ignition Timer Threshold...
  • Page 31: F14 Recommendations For A Long Ups Service Life

    F17 Disclaimer We, the Bicker Elektronik GmbH, have checked the contents of this document for compliance with the hard- ware and software described. Nevertheless, deviations can not be ruled out, so we assume no liability for the complete agreement. The information in this publication is checked regularly, necessary corrections are inclu- ded in the updated versions.
  • Page 32 Bicker Elektronik GmbH Ludwig-Auer-Straße 23 86609 Donauwörth · Germany Tel. +49 (0) 906 70595-0 Note: Subject to errors and technical modifications! +49 (0) 906 70595-55 Windows® is a registered trademark of the Microsoft Corp. E-Mail info@bicker.de Status as at: 26.05.2021 – Revision 1...

This manual is also suitable for:

Ip65Ip67Upsi-1208ip-11uUpsi-2406ip-12u

Table of Contents