User Manual UPSI-2412DPx
UPS SYSTEM
DIN-RAIL
Bicker Elektronik GmbH
Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPSI-2412DP Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bicker Elektronik UPSI-2412DP Series

  • Page 1 English User Manual UPSI-2412DPx UPS SYSTEM DIN-RAIL Bicker Elektronik GmbH Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany...
  • Page 2 UPSI-2412DPx Legend of used symbols Symbol Description Attention! Important hazard warning. Do not dispose of in the domestic waste. Warning of electrical voltage. Revision Directory Date Change 25.02.2021 Initial version Revision 0-1 31.03.2021 Release version Revision 1 01.04.2021 F13 Shutdown diagram added Revision 1-1 Revision 1-1...
  • Page 3 UPSI-2412DPx Revision 1-1...
  • Page 4: A Brief Specification Upsi-2412Dp2 / Upsi-2412Dp3

    UPSI-2412DPx A Brief specification UPSI-2412DP2 / -DP3 24 V DC / 10 A Powerful 24 V DC UPS (DIN rail version)  Integrated maintenance-free Supercaps (DP2)  OR LiFePO4 battery (DP3) Up to 500 000 cycles (DP2) |  up to 5 000 cycles (DP3) Capacity DP2: 13.5 kJ | DP3: 64 Wh ...
  • Page 5 UPSI-2412DPx Backup time* UPSI-2412DP2 Backup time BP-SUC-30090 Backup time* UPSI-2412DP3 Backup time BP-LFP-2725 *Backup time depends on battery capacitance, load and temperature. At very high or low temperatures a reduction of backup time occurs. Unless otherwise specified, the values apply to measurements at +25 °C Revision 1-1...
  • Page 6: Table Of Contents

    UPSI-2412DPx Brief specification UPSI-2412DP2 / UPSI-2412DP3 ..........4 Introduction and description ................7 B1 Description of the product and its functions ....................7 B2 Intended use .................................8 Safety instructions ....................9 Technical Data ..................... 10 D1 General Technical Data ............................10 D2 Drawing UPSI-2412DP2 / UPSI-2412DP3 ....................
  • Page 7: B Introduction And Description

    UPSI-2412DPx B Introduction and description Read carefully before initial operation ! This manual shall help the user to get familiar with the product and its components and features. It shall pro- vide information as accurately and completely as possible. The manual as well as all documents has to be read and followed strictly before installation. Otherwise in cer- tain situations warranty and guarantee can be cancelled partly or completely.
  • Page 8: B2 Intended Use

    UPSI-2412DPx B2 Intended use This device is designed to be installed into a suitable enclosure which protects against electrical, water and fire hazards and can then be used indoors and outdoors. It is primary built for being mounted on a DIN Rail and is intended for professional use in applications such as industrial control, communication and measurement technology.
  • Page 9: C Safety Instructions

    UPSI-2412DPx C Safety instructions WARNING! Disregarding of following issues can result in electric shock, fire, serious injury or death. 1. Care must be taken to ensure proper and professional wiring. 2. The device pack must not be exposed to fire and temperatures outside the specification. 3.
  • Page 10: D Technical Data

    UPSI-2412DPx D Technical Data D1 General Technical Data INPUT DATA – UPSI-2412DP2 / UPSI-2412DP3 Unless otherwise stated, all specifications apply to 25° C ambient temperature, 24 V DC input voltage and nominal output current (I Input voltage 24 V DC Input voltage range 22.8 V DC…30 V DC Electric strength max.
  • Page 11 UPSI-2412DPx OUTPUT DATA – UPSI-2412DP2 / UPSI-2412DP3 (NORMAL MODE) Unless otherwise stated, all specifications apply to 25° C ambient temperature, 24 V DC input voltage and nominal output current (I Output voltage 24 VDC Output voltage range – 0.6 VDC max. (depending on load) Capacitive load 10 000 µF (at start / 0 A output load) Output current...
  • Page 12 UPSI-2412DPx CONNECTION DATA INPUT / OUTPUT Connection method Screwable plug connector Conductor cross-section solid 0.205 mm² … 3.31 mm² (24 … 12 AWG) Conductor cross-section flexible 0.205 mm² … 3.31 mm² (24 … 12 AWG) Conductor cross-section with ferrule 0.205 mm² … 3.31 mm² (24 … 12 AWG) Stripping length 7 mm …...
  • Page 13 UPSI-2412DPx CONNECTION DATA – RELAY Connection labeling Switch contact (potential free) Relay Status (configurable) Power Fail Alarm Switching voltage 24 V DC / 125 V AC Current carrying capacity 1A (DC) / 0.5 A (AC) State - signal assignment NO (Normally Open) / NC (Normally Closed) – configurable via Software DATA INTERFACE –...
  • Page 14 UPSI-2412DPx DATA INTERFACE – RS232 Interface designation RS232 Numbers of interfaces Connection method DSUB 9-Pin (female) Locking Transmission physics RS232 light (TX / RX) Topology Point-to-point Symbol rate (baud rate) 38400 Type of cable Transmission length ≤10 m Access time <1 s Voltage level -6 V DC …...
  • Page 15 UPSI-2412DPx ENVIRONMENTAL CONDITIONS Ambient temperature (operation) DP2: -20… +70° C / DP3: -20… +55 C Ambient temperature (start up without load) DP2: -30° C / DP3: -20° C Ambient temperature DP2: -30…+70° C / DP3: -30…+55° C (storage / transport) Max.
  • Page 16 UPSI-2412DPx INTERFERENCE IMMUNITY ACCORDING TO EN 61000 (INDUSTRY) Basic standard CE Fulfilled requirements according to EN 61000 (CE) (Interference immunity of industrial environment) Electrostatic discharge EN 61000-4-2 Contact discharge 4 kV Air discharge 8 kV Comment Criterion A Electromagnetic HF field EN 61000-4-3 Frequency range 80 MHz …...
  • Page 17 UPSI-2412DPx EMISSION ACCORDING TO EN 61000-6-4 (INDUSTRY) Basic standard CE Fulfilled requirements according to EN 61000-6-4 (CE) (Industrial environment) Conducted emission from the power port EN 61000-6-4 Frequency range 150 kHz–30 MHz Comment Conform Electric field radiated emission EN 61000-6-4 Frequency range 30 MHz–1 GHz Comment...
  • Page 18: D2 Drawing Upsi-2412Dp2 / Upsi-2412Dp3

    131 mm 111 mm 8...9 mm E Name / Address / Support E-Mail / Phone number of the manufacturer Bicker Elektronik GmbH · Ludwig-Auer-Straße 23 · 86609 Donauwörth · Germany E-Mail: support@bicker.de · Tel.: +49 (0) 906 70595-0 Revision 1-1...
  • Page 19: F General Data

    UPSI-2412DPx F General Data F1 Assembly and installation advice Installation and operation of this device is only allowed to be executed by a qualified electrician! The application has to be separated from any power during the mounting process. Wires have to be connected safely and must not have contact with sharp edges. Pay attention to correct polarity! Before commissioning, check all the connections for correctness! F2 Convection and installation position For these DIN rail versions, vertical mounting on a horizontal rail (DIN rails according to EN 60715) is recom-...
  • Page 20 UPSI-2412DPx DIN-Rail mounting and DIN-Rail profile according to EN 60715    Press down  Revision 1-1...
  • Page 21: F3 Description Of Connectors

    UPSI-2412DPx F3 Description of connectors INPUT & OUTPUT (IN & OUT) FUNCTION Vin + Vin – Vout – Vout + RELAY CONNECTION (RL) The function of the relay connection is configurable via software. When closing the relay the resistor value between both contacts is approx. 0 Ω, otherwise they are „open load“. FUNCTION Relay contact 1 Relay contact 2...
  • Page 22: F4 Dimensioning The Upstream Power Supply

    UPSI-2412DPx F4 Dimensioning the upstream power supply Ensure that the upstream power supply is correctly dimensioned to guarantee the charging process of the bat- teries and the correct functioning of the application. The input has to be supplied from a SELV or PELV power supply.
  • Page 23: F5 Connecting Diagram

    UPSI-2412DPx F5 Connecting diagram APPLICATION – – RELAY RS232 (DSUB 9) for individual use CONNECTING ORDER 1. APPLICATION (V 2. DC SOURCE (V 3. RELAY / USB / RS232 Dismantling order reverse to connection! – ATTENTION! 1. Note polarity! 2. AWG16 wire should be used (1.5 mm Revision 1-1...
  • Page 24: F6 Initial Operation

    UPSI-2412DPx F6 Initial operation The correct installation of the UPS has to be ensured. After that, the start can take place in two ways: 1. By connecting the supply voltage (standard): If a voltage more than 22.8 V is connected to the input terminals, the energy storage is queried and trans- mits its data.
  • Page 25: F7 Overview Connector / Counterpart With Part No. / Scope Of Delivery

    UPSI-2412DPx F7 Overview connector / counterpart with description / Scope of delivery CONNECTOR PART NO. COUNTERPART NO. Würth Elektronik 691317510004 Würth Elektronik 691340500004 Würth Elektronik 68800211722 Würth Elektronik 688002113322 Würth Elektronik 61400416121 USB type B connector RS232 D-Sub9 Female D-Sub 9 Male SCOPE OF DELIVERY QUANTITY DESCRIPTION...
  • Page 26: F10 Backup Time

    UPSI-2412DPx F10 Backup time in battery mode The nominal backup times can be found within the technical data of this user manual or the user manu- als / datasheets of the used energy storages. At extreme low or high temperatures a reduction of the nominal backup times can occur.
  • Page 27: F13 Status Led

    UPSI-2412DPx F13 Status LED Valid from firmware version 2.2.6 MAIN STATES Always on Status: mains voltage >> Mains voltage is present. 1 Hz flash Status: Battery mode (1 s on, 1 s off) >> Mains voltage is not present. INTERNAL STATES Status: Battery start 1 x flash (LED is off briefly), pause 2 s...
  • Page 28: F14 Shutdown Diagram

    UPSI-2412DPx F14 Shutdown diagram False Power Fail True Ignition-Timer True Enabled False Shutdown SOC Max. Backup Shutdown-Timer Ignition Pin False Enabled Enabled OS Enabled High True True True True False False Shutdown SOC Max. Backup Shutdown-Timer Ignition Timer Threshold Time Timeout Timeout Timeout Reached...
  • Page 29: F14 Recommendations For A Long Ups Service Life

    F18 Disclaimer We, the Bicker Elektronik GmbH, have checked the contents of this document for compliance with the hard- ware and software described. Nevertheless, deviations can not be ruled out, so we assume no liability for the complete agreement. The information in this publication is checked regularly, necessary corrections are inclu- ded in the updated versions.
  • Page 30: F18 Preventive Measures And Rules When Operating The Ups System

    UPSI-2412DPx F19 Preventive measures and rules when operating the UPS system The voltage drop of the supply line has to be kept in mind! The maximum charge current can cause huge vol- tage drops if too long supply lines are used. If the voltage drop is too high a shortfall of the threshold values is possible and a not intended Power Fail could be caused.
  • Page 31 Bicker Elektronik GmbH Ludwig-Auer-Straße 23 86609 Donauwörth · Germany Tel. +49 (0) 906 70595-0 Note: Subject to errors and technical modifications! +49 (0) 906 70595-55 Windows® is a registered trademark of the Microsoft Corp. E-Mail info@bicker.de Status as at: 01.04.2021 – Revision 1-1...