Control cabinet design and cooling

Closed control cabinet with
air circulation
P
~ 400 W
Q
Requirements for control cabinets
with fan
Bosch Rexroth AG R911335703_Edition 04
G1 is the only mounting position allowed for supply units and
drive controllers installed in control cabinets.
Possible ways of heat dissipation
Closed control cabinet with
heat exchanger
P
~ 1700 W
Q
P
Dissipated heat output
Q
Tab. 4-11:
Possible ways of heat dissipation
The section below describes the "control cabinet with fan".
NOTICE
Operating a control cabinet with a fan, but without the corresponding filters,
can damage the devices or cause malfunction.
Install filters at the air intake opening of the control cabinet so that
unclean air cannot get into the control cabinet.
Service the filters at regular intervals according to the dust loading in the
environment.
Only replace the filters when the fan has been switched off, because
otherwise the fan sucks in the dirt coming off the filter and the dirt gets
into the control cabinet.
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Control cabinet with fan
P
~ 2700 W
Q
Risk of damage by unclean air in the control
cabinet!
Closed control cabinet with
air conditioning unit
P
~ 4000 W
Q