8.2.4
Grounding terminal of the FX
The grounding terminal of the FX
1. Applicable cables
Electric wire size
0.5 to 1.5 mm
2. Treatment of electric wire ends
• When using a stranded cable or solid cable as it is
- Twist the end of the stranded cable so that loose wires will not stick out.
- Do not solder-plate the end of the cable.
3. Tightening torque
Set the tightening torque to 0.4 to 0.5 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
Caution
When tightening a grounding terminal, use a screwdriver suitable for the terminal screw. The screwdriver
which does not suit the thread groove is used, tightening torque will not be able to be achieved. To achieve
the appropriate tightening torque shown in the above, use the following screwdriver or an appropriate
replacement.
<Reference>
Weidmuller Interface GmbH & Co. KG
Weidmuller Interface GmbH & Co. KG
70
3U
-ENET-ADP is a M2.5 screw.
3U
2
(AWG 20 to 16)
Approx. 8 mm
(0.31")
Manufacturer
8 Preparation for Wiring and Power Supply Wiring Procedures
-ENET-ADP
Model name
SDIK PH0
SD 0.6×3.5×100
8.2 Cable Connecting Procedures
Model number
9008560000
9008330000