Mitsubishi Electric MELSEQ FX3S Series User Manual page 142

Hide thumbs Also See for MELSEQ FX3S Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3S
User's Manual - Hardware Edition
PLC
Error
operation
code
at error
occurrence
Parameter error [M8064 (D8064)]
0000
-
No error
6401
Program sum check error
6402
Memory capacity setting error
6404
Comment area setting error
6405
File register area setting error
Stops
6420
Special parameter sum check error
operation
6421
Special parameters setting error
Syntax error [M8065 (D8065)]
0000
-
No error
Incorrect combination of instruction, device symbol and device
6501
number
No setting value after OUT T or OUT C.
6503
Insufficient number of operands for an applied instruction.
Same label number is used more than once.
6504
Same interrupt input or high-speed counter input is used
Stops
more than once.
operation
6505
Device number is out of allowed range.
6506
Invalid instruction
6507
Invalid label number [P]
6508
Invalid interrupt input [I]
6510
MC nesting number error
Circuit error [M8066 (D8066)]
0000
-
No error
6610
LD, LDI is continuously used 9 times or more.
6611
More ANB/ORB instructions than LD/LDI instructions
6612
Less ANB/ORB instructions than LD/LDI instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
Stops
No coil between MPS, MRD and MPP, or incorrect
6616
operation
combination
Instruction below is not connected to bus line:
6617
STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET, FEND
or END
STL, MC or MCR can be used only in main program, but it is
6618
used elsewhere (e.g. in interrupt routine or subroutine).
Invalid instruction is used in FOR-NEXT loop:
6619
STL, RET, MC, MCR, I (interrupt pointer) or IRET.
136
14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
Contents of error
Action
STOP the PLC, and correctly set the parameters.
STOP the PLC, and correctly set the special parameters.
Set special parameters correctly, turn OFF the power, and
then turn ON the power.
Check the contents of the special parameter error code
(D8489), confirm troubleshooting for special adapters/
special blocks, and set special parameters correctly.
Set special parameters correctly, turn OFF the power, and
then turn ON the power.
During programming, each instruction is checked. If a syntax
error is detected, modify the instruction correctly.
This error occurs when a combination of instructions is
incorrect in the entire circuit block or when the relationship
between a pair of instructions is incorrect.
Modify the instructions in the program mode so that their
mutual relationship becomes correct.

Advertisement

Table of Contents
loading

Table of Contents