Mechanical Safety - Huawei UPS2000-G-6 kVA User Manual

Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
Harmful Gas
Do not use unsealed lead-acid batteries. Lead-acid batteries emit flammable gas. Therefore,
place and secure lead-acid batteries horizontally to prevent fire or corrosion.
Store lead-acid batteries in a place with good ventilation, and take fire safety precautions.
Battery Temperature
High temperature may result in battery distortion, damage, and electrolyte overflow.
Electrolyte Leakage
In the case of electrolyte leakage, counteract and absorb the leaking electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte
may harm human bodies. If the electrolyte leaks, use the following substances to counteract
and absorb the leaking electrolyte:
When using substances to counteract and absorb electrolytes, strictly follow the guidelines
provided by the battery manufacturer.
If any personnel are exposed to battery electrolyte, wash the exposed area with clean water
immediately and seek medical advice if the situation is serious.

1.5 Mechanical Safety

Moving Sharp Objects
Issue 13 (2019-05-05)
Install or store batteries far away from fire sources and heating devices such as
transformers. Never burn batteries.
If the battery temperature exceeds 60° C, check the battery for electrolyte overflow. If
electrolyte overflows, handle the leakage immediately.
Sodium bicarbonate (baking soda): NaHCO
Sodium carbonate (soda): Na
Copyright © Huawei Technologies Co., Ltd.
3
CO
2
3
1 Safety Precautions
8

Hide quick links: