UPS2000-G-(6 kVA-20 kVA)
User Manual
D
Alarm Handing of Battery Maintenance
Context
If no battery shallow discharge test is performed within 60 days after a UPS2000-G is
installed and the maintenance notification time has arrived, the mains indicator is on, the
battery and bypass indicators are off, the fault indicator on the info key are blinking red, and
alarms are generated intermittently.
Procedure
Step 1 Clear the Batt. maint. notif alarm.
1.
2.
Issue 13 (2019-05-05)
Press the i key on the UPS control panel to display the Active Alarms page. If multiple
active alarms exist, use the ▲ or ▼ key to select the alarm record on the top (the latest
alarm is on the top by default). Press
Figure D-1 Viewing alarms
Press
to display the Maintain Batteries screen. Then the Batt. maint. notif alarm
disappears and timing for the next notification starts, regardless of whether you perform
a discharge test. The battery maintenance notification 0036-01 in the active alarm menu
will disappear.
Copyright © Huawei Technologies Co., Ltd.

D Alarm Handing of Battery Maintenance Notification

to view the alarm ID and name.
Notification
131