UPS2000-G-(6 kVA-20 kVA)
User Manual
Figure 4-14 Battery Status screen
Inverter Output Screen
Figure 4-15
Figure 4-15 Inverter Output screen
UPS Output Screen
Figure 4-16
Issue 13 (2019-05-05)
Battery voltage parameter
Battery string voltage (positive and negative battery string voltages in the case of the
UPS2000-G-15 kVA/20 kVA)
Battery current parameter
Battery string current (positive and negative battery string currents in the case of the
UPS2000-G-15 kVA/20 kVA). + is displayed during battery charge, and – is displayed
during battery discharge.
Status parameter
The battery status is NA (battery not connected or reversely connected), Equalized
charging, Float charging, Hibernating, or Discharging.
Capacity parameter
Remaining battery capacity
Backup time parameter
Estimated backup time. The value is NA during battery charge.
shows the Inverter Output screen.
Van, Vbn, and Vcn parameters
Phase voltages displayed on the Inverter Output screen (The parameter is Voltage in
the case of single-phase input.)
la, lb, and lc parameters
Phase currents displayed on the Inverter Output screen (The parameter is Current in
the case of single-phase input.)
Frequency parameter
Frequency displayed on the Inverter Output screen.
shows the UPS Output screen.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
45