UPS2000-G-(6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
Inverter
0060-07
fault
0060-08
Inverter
fault
Inverter
0061-01
alarm
Issue 13 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Automati
Critical
c clear
Critical
Manual
clear/Po
wer-off
clear
Manual
Minor
clear/Po
wer-off
clear/Aut
omatic
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
The UPS starts upon
shutdown.
The UPS may transfer to
another working mode or
shut down.
The UPS shuts down.
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
C Alarm Handling
Repair Proposal
mode is not set.
The hardware is faulty.
Measures:
After you rectify the fault,
restart the UPS.
Check whether the load type
is supported by the UPS.
Enable the transformer mode.
Contact Huawei technical
support for repair.
Possible causes:
The ambient temperature
exceeds 40º C.
The air channel is blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign objects
around the fan. If the alarm
persists, contact Huawei
technical support for repair.
Possible cause: The DSP or
CPLD chip is faulty.
Measure: Contact Huawei
technical support for repair.
Possible causes:
Parallel cables are incorrectly
connected.
The lengths of parallel cables
vary greatly.
Measures:
Reconnect cables.
The lengths of parallel cables
vary within a range of 5%.