UPS2000-G-(6 kVA-20 kVA)
User Manual
The UPS has no built-in backfeed protection device. You can install a backfeed protection
device on the input front side.
If you do no install a backfeed protection device on the input front side, attach a warning label
to the main power isolation device. The label reads like this: "This circuit supplies power to
the UPS. Before cable connection, disconnect the UPS, and check the voltage across wiring
terminals."
When battery mode is unavailable or the mains fails, the UPS internal voltages or energy may
flow back directly, or through a leakage path, to an input terminal. To minimize the risk of
electric shocks, install a backfeed protection device on the input side.
Table 3-3 Rated voltages and currents for backfeed protection contactors
Model
UPS2000-G-6KRTS
UPS2000-G-6KRTL
UPS2000-G-10KRTS
UPS2000-G-10KRTL
UPS2000-G-15KRTL
(three-phase input)
UPS2000-G-20KRTL
(three-phase input)
UPS2000-G-15KRTL
(single-phase input)
UPS2000-G-20KRTL
(single-phase input)
Table 3-4 Control relay parameters
Recommended Model
HF18FF/012 (HONGFA control relay)
MY2N-J DC12V (OMRON control relay)
HJ2-L-DC12V (Panasonic control relay)
Issue 13 (2019-05-05)
Rated Voltage and Current
220/230/240 V AC, 40 A
220/230/240 V AC, 65 A
220/230/240 V AC, 32 A
220/230/240 V AC, 40 A
220/230/240 V AC, 125 A
Copyright © Huawei Technologies Co., Ltd.
Recommended
Contactor Models
(Schneider contactors)
LC1-D40A
LC1-D50A for
single-phase input
LC1-DT60A for
three-phase input
LC1-D80 for
single-phase input
LC1-DT60A for
three-phase input
Parameters
Dry contact: NC
Breaking capability: 250 V AC, 5 A
Coil: 12 V rated voltage; rated current of
less than 1 A
3 Installation
30