Huawei UPS2000-G-6 kVA User Manual page 137

Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
0135-01
Ambient
underhu
midity
0136-01
Faulty
temperat
ure and
humidity
module
0158-01
On
bypass
0159-01
On
battery
Issue 13 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Minor
Minor
Minor
Automati
c clear
Minor
Automati
c clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
If the bypass is abnormal,
the UPS may power off.
The UPS may power off if
batteries are abnormal.
C Alarm Handling
Repair Proposal
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient humidity
of the UPS equipment room.
Replace the temperature and
humidity transducer.
Possible causes:
The ambient humidity in the
UPS equipment room is
below the alarm threshold
(default value: 10%).
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient humidity
of the UPS equipment room.
Replace the temperature and
humidity transducer.
Possible causes: The temperature
and humidity module is faulty.
Measures:
Check parameter settings of
the temperature and humidity
transducer.
Replace the temperature and
humidity transducer.
Possible causes:
The inverter is not started.
The load exceeds the rated
inverter loading capacity.
The inverter is faulty.
Measures:
Check whether other alarms
are generated. If yes, see the
other handling methods.
If no, start the UPS manually.
Possible causes:
The mains input is abnormal.
129