Pipes In Cascade - Baxi POWER HT+ Series Installation And Service Manual

Gas fired floor-standing condensing boiler
Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

Fig.49
Specifications of the separate pipes for POWER HT+ 1.90 and POWER HT+ 1.110
115
170
115
354,5
600
Tab.15 Flue system for boilers in cascade
Boiler model
POWER HT+ 1.50
POWER HT+ 1.70
POWER HT+ 1.90
POWER HT+ 1.110
7609474 - v02 - 04092014
245,5
Maximum number of boilers in cascade
Diameter 125 mm (200 kW
max)
4
2
/
/
112
584
MW-3000126-01
This type of pipe is used to discharge combusted gases either to the out­
side of the building or into the individual flue gas pipes. Combustive air
can be taken in from zones different from the discharge zones. The two-
way accessory includes a discharge fitting Ø 110 mm and an air intake fit­
ting Ø 110 mm.
The 90° elbow is used to connect the boiler to the discharge and intake
pipes according to requirements. It can also be used as an extra elbow to
couple to the pipe or to the 45° elbow.
Insertion of a 90° elbow reduces the total length of the pipe by 0.5 me­
tres.
Insertion of a 45° elbow reduces the total length of the pipe by 0.25 me­
tres.
The first 90° elbow is not taken into account in calculating the maximum
length available.

6 6 .5.4 Pipes in cascade

These types of pipes are used to discharge the combustion products from
several boilers interlinked in cascade via a shared flue gas collector. The
collector must be used solely to connect the boilers to the flue gas pipe.
The diameters available are 150 mm and 200 mm. A range of accessories
is available on request.
Diameter 160 mm (250 kW
max)
5
3
2
2
Caution
For this type of extraction, each boiler must be fitted with a flue
gas valve (non-return valve) Ø 110/110 mm.
Caution
The calculation of the length of the flue gas pipe must be made by
a qualified technician during the system design phase, in accord­
ance with the requirements of the prevailing standards.
See
Fan speed according to gas type, page 59.
6 Installation
Diameter 200 mm (500 kW
max)
10
7
5
4
45