TECHNICAL SPECIFICATIONS

Supply: - 115/230 VAC (-18%, +8%),50/ 60 Hz, overload and over-
voltage protection fuse F10-1A fast blow.
- 12 VDC for AC back-up supply; can activate all outputs if supplied
with DC back-up voltage.
Fan output 1:
ON-OFF output, 115/230 VAC, 50/60 Hz, 10A RES, 1/2 HP (373W) ,
fuse F6-10A slow blow.
Fan output 2:
ON-OFF output, 115/230 VAC, 50/60 Hz, 10A RES, 1/2 HP (373W) ,
fuse F5-10A slow blow.
Fan output 3:
ON-OFF output, 115/230 VAC, 50/60 Hz, 10A RES, 1/2 HP (373W) ,
fuse F4-10A slow blow.
Heater output:
ON-OFF output, 115/230 VAC, 50/60 Hz, 10A RES, 1/2 HP (373W) ,
fuse F7-10A slow blow.
Curtain output:
ON-OFF output, 115/230 VAC, 50/60 Hz, 10A RES, 1/2 HP (373W) ,
fuse F2-10A slow blow.
Alarm: ON-OFF output, 115/230 VAC, 50/60 Hz, 30VDC, 3A ,
fuse F9-3A slow blow.
Probes: Low voltage ( < 5V), isolated from the supply. Operating range:
-40.0° to 120.0°F (-40.0° to 48.9°C). Accuracy: 1.8