TEST MODE

A test mode allows you to simulate temperature changes and verify con-
troller performance. In test mode, the temperature probe inputs are turned
off, allowing the user to change the temperature used by the controller to
operate the outputs. The controller operates as before using the new tem-
perature settings.
To enter test mode:
Set the function to ROOM TEMPERATURE using the function selector
buttons. The current room temperature is displayed.
Press and hold the second functions push-button for 3 seconds. The
letters "tESt" are displayed, alternating with the room temperature.
Use the adjustment buttons to adjust the room temperature to the
desired value. The controller operates the stages according to the
new temperature setting.
To exit test mode:
Set the function to ROOM TEMPERATURE using the function selector
buttons. The current room temperature is displayed.
Press and hold the second functions push-button for 3 seconds.
NOTE: If no user activity is recorded after 4 minutes in test mode, the
controller resumes normal operation.