TEMPERATURE CURVE

The user can define a temperature curve to adjust the set point automati-
cally over a given time period. This function is only used when the thermo-
stat controller operates as a stand-alone unit (i.e. when no temperature
controller is detected).
A curve is defined using six points. Each point specifies a day number and
a set point for that day. Once the points of the curve are defined, the curve
must be activated. The controller will change the temperature set point
every hour in a linear fashion between consecutive points of the curve.
When the last point of the curve is reached, the temperature set point for
that day is maintained until the curve is reactivated.
Temperature
T
1
o
T
2
o
T
3
o
T
4
o
T
5
o
T
6
o
NOTES :
i) All six points of the curve must be specified. If six points are not needed,
repeat the last temperature value for each unnecessary point.
ii) Certain restrictions apply to reduce the risk of errors:
- The highest possible day number is 99.
- Decreasing day numbers are not allowed.
- Increasing temperatures are not allowed.
- The temperature variation cannot exceed 3°F (1.6°C) per day.
d4
d35
d25
SMART THERMOSTAT
d50
SMART THERMOSTAT rev.01
d80
d70
Days
17