Dst On/Off; Ds Setup; Run/Soak; Sensor - Weathermatic SmartLine SL800 Owner's Manual

Hide thumbs Also See for SmartLine SL800:
Table of Contents

Advertisement

5.0 Advanced Menu
18

5.19.1 DST ON/OFF

If you would like for your controller to automatically set the time
of day on the occurrence of Daylight Saving Time, make sure it
is turned on in this menu

5.19.2 DS SETUP

Your controller is programmed with the a default of starting
Daylight Saving Time starting on the second Sunday in March
and ending on the first Sunday in November. If you would like to
adjust these settings, you may do so in this menu.

5.20 RUN/SOAK

The purpose of Run/Soak is to break up long run times that
often cause wasteful runoff. The Run/Soak is programmable for
each program if you are using the BASIC watering mode. Note:
If you are using SMART, these inputs are not used since the Run/
Soak period is automatically calculated.
Turn the dial to Advanced Menu and use the UP button to
navigate to RUN/SOAK. Press the NEXT button and the screen
will display RUN, now press the PGM button to select the
program you wish to set the RUN feature. After the program
has been selected, press the NEXT button and then using the
UP or the DOWN button adjust the RUN value. **NOTE: the RUN
time can be set from OFF to 30 minutes (SmartLine® controller
default is OFF). Once completed, press the BACK button and the
screen will again display RUN, now press the UP or the DOWN
button and the screen will display SOAK. Press the NEXT button
to enter the SOAK feature and then using the UP or the DOWN
button adjust the SOAK value. **Note: the SOAK time can be set
from OFF to 2 hours in one-minute increments. Repeat these
steps for adjusting multiple programs within the panel.
http://support.weathermatic.com
5.21

SENSOR

Sensor is an ON/OFF toggle to override the SEN terminals rain/
freeze functions on selected zones. Factory default is ON.

5.22 MIN DEF

This feature allows a Minimum Deficit to be set. The feature
requires that a zone deficit be greater than the MIN DEF setting
in order to run during a scheduled program. The setting is
global for all zones in SMART. The range for the global setting is
0.00 to 0.50 inches. The factory default is 0.15 inches.

5.23 FLOW

The Flow menu must be accessed by first activating a SmartLink
Flow Aircard connected to the controller.

5.23.1 HIGH PK

Shows the highest flow value for each individual zone, can scroll
through each zone for a 7-day history.

5.23.2 CLR FLOW

Clears All flow data from the controller.

5.23.3 SETTINGS

Allows the user to set Flow parameters.
5.23.3.1
FLOW PPG
A settable value that lets the controller know how many
pulses to expect per gallon.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartline sl1600Smartline sl1620Smartline sl4800

Table of Contents