TECHFASS APS mini MREP 78 Series User Manual

TECHFASS APS mini MREP 78 Series User Manual

Reader modules for wall-mounting, for bpt xolid panels nad for oem use in own applications

Advertisement

Quick Links

MREP 78
APS mini Plus reader modules for wall-mounting, for BPT Xolid panels nad for
OEM use in own applications
User's guide
© 2004 – 2019, TECH FASS s.r.o., Věštínská 1611/19, 153 00 Prague, Czech Republic, www.techfass.cz, techfass@techfass.cz
(Date of release: 2019/06/03, valid for FW version 5.12)

Advertisement

Table of Contents
loading

Summary of Contents for TECHFASS APS mini MREP 78 Series

  • Page 1 APS mini Plus reader modules for wall-mounting, for BPT Xolid panels nad for OEM use in own applications User’s guide © 2004 – 2019, TECH FASS s.r.o., Věštínská 1611/19, 153 00 Prague, Czech Republic, www.techfass.cz, techfass@techfass.cz (Date of release: 2019/06/03, valid for FW version 5.12)
  • Page 2: Table Of Contents

    1 Content 1 Content ........................2 2 Product description ..................... 3 MREP 78 module ....................3 MREP 78X module ....................3 MREP 78E module ....................3 3 Technical parameters ....................4 Product version ....................4 Technical features....................5 Special accessories ..................... 5 Using WIO 22 module for remote output control ..........
  • Page 3: Product Description

    2 Product description MREP 78 reader modules (125 kHz readers with an embedded single door controller) are designed for connection to the RS 485 bus of the APS mini Plus access control system, or for standalone operation. It is possible to connect up to 32 reader modules to a single line of the APS mini Plus system.
  • Page 4: Technical Parameters

    Wall-mounted 53478401 ✓ ✓ MREP 78X – EM Xolid panel 53478411 ✓ ✓ MREP 78E – EM OEM solution 53478421 Table 1: Product version – TECHFASS factory 125 kHz ID media reading; – 125 kHz ID media reading; Page 4...
  • Page 5: Technical Features

    3.2 Technical features 8 ÷ 28 VDC Supply voltage Typical 70 mA Current demand Maximal 120 mA Keypad layout Numeric keypad, 12 keys ID technology, EM Marin 5 cm (with ISO card) typical reading range Real-time clock Yes, with 24 hrs. back-up Cards 2,000 ID, 2 programming cards Memory...
  • Page 6: Mechanical Design

    3.5 Mechanical design MREP 78 0.420 kg Weight MREP 78X 0.306 kg MREP 78E 0.129 kg -25 ÷ 60 °C Operating temperature Humidity Max 95%, non-condensing Housing IP 54, IK 07 Pigtail (MREP 78) Environment Indoor and outdoor MREP 78 115 x 62 x 35 mm Dimensions MREP 78X...
  • Page 7: Led Indicators Description

    4.2 LED indicators description Communication status, ID media reading Door lock status, programming mode IDS monitoring Table 7: LED indicators Pic. 3: LED indicators description Continuously lit – RED Online operating mode Flashing with 4 s period – RED Offline operating mode Fast switching –...
  • Page 8: Installation Instructions

    The door monitoring contact (IN1) is operational after its first change of status since switching on the module. Full door lock timing acc. to tab. 10 is used when the door status contact is not installed and no Forced Door and Door Ajar alarms are triggered. 4.4 Installation instructions The reader module uses passive RF/ID technology, which is sensitive to RF noise sources.
  • Page 9: Setting Parameters Of The Reader Module

    Enabled / Disabled Enabled Strike closed Enabled / Disabled Enabled Table 10: Configurable parameters 5.2 Reader module parameters setting Detailed instructions for setting reader module parameters are described in the APS Reader configuration program user’s guide available address http://www.techfass.cz/files/m_aps_miniplus_reader_en.pdf. Page 9...
  • Page 10: Reader Module Functioning

    6 Reader module functioning The reader module supports the following functions: • Standard “Door Open” function. • Door status monitoring. • Exit-devices contact monitoring. • Alarm output activated / acoustic signalization activated when any alarm condition occurs. • IDS control in the relevant operating mode using the WIO 22 relay module The “Door Open”...
  • Page 11: Alarm States

    6.3 Alarm states The reader module can get in following alarm states: 1) Tamper alarm 2) Forced door alarm 3) Door ajar alarm 4) Antipassback alarm (Time APB alarm, Zone APB alarm) 5) ID with Alarm flag alarm, Duress PIN alarm Alarm state reporting is performed as follows: •...
  • Page 12: Standard Operating Modes

    – in combined systems with WIEGAND output readers with a fixed user’s guide available at WIEGAND data format IDs (more information in APS Reader http://www.techfass.cz/files/m_aps_miniplus_reader_en.pdf). 6.6 Wiegand interface configuration (operating mode) 6.6.1 Standard operating mode In the...
  • Page 13 When the reader module operates in the entry reader operating mode, the I/O Port (tab. 6 is used as an output for controlling the entry reader buzzer. Since the FW version 5.09 the reading synchronization of a couple of TECHFASS readers implemented, enabling to cancel the mutual disturbance of the modules. The reader module offers the...
  • Page 14: Keypad Function

    Code 0 Table 13: Key codes sent in WIEGAND output operating mode Since the FW version 5.09 the reading synchronization of a couple of TECHFASS readers implemented, enabling to cancel the mutual disturbance of the modules. The reader module offers the...
  • Page 15: Programming Mode

    Keypad configuration Key pressed PIN / ID keypad Key code keypad Keys 1  9 (digits) Digits 1  9 Reason 1  9 Key 0 Digit 0 Reason 10 Key  (star) Digits input cancel Reason 0 Key # (hash) Input submit (enter) Reason 11 Table 14: Pressed key interpretation...
  • Page 16 6.8.1 Inserting cards (codes) into the reader’s memory Follow these steps for inserting cards into the reader module’s memory: Step 1 Step 2 Step 3 Read the programming card One by one, read the cards About seconds after (or enter the programming (enter user codes) which are inserting the last card (code) code) for inserting: the reader...
  • Page 17 6.8.3 Deleting cards (codes) „above or below“ If a user loses his ID medium, it is usually impossible to delete the ID from the memory with the procedure described in the previous chapter, since the medium is no longer available (with an exception of entering the code at the keypad).
  • Page 18 6.8.4 Deleting all cards (codes) from the reader’s memory Follow these steps for deleting all cards from the reader module’s memory: Step 1 Step 2 Step 3 Read the programming card Read the programming card The reader module goes (or enter the programming for deleting 5 times in a row back into standard operating...
  • Page 19: Id Expiration Function

    • – Delete it Card 4 gets lost using the card 2, which is available, and using the procedure from chapter 6.8.3 – Read + (inserting) programming card, then 5x + (inserting) programming card again, then card 2, and finally + (inserting) programming card again.
  • Page 20: Id With Alarm Flag Function

    6.10 ID with Alarm flag function This function is implemented since the FW version 5.0. Alarm – ID flag It is possible so set an for every stored in the module. When the ID is read, relevant alarm is raised (and the alarm output is switched for preset time). 6.11 Antipassback function This function is implemented since the FW version 5.0.
  • Page 21: Duress Pin

    The disabling status changes and disabled actions are logged in the events archive. 6.14 Reading synchronization Since the FW version 5.09 the reading synchronization of a couple of TECHFASS readers implemented, enabling to cancel the mutual disturbance of the modules. The reader module offers to use the IO synchronization...
  • Page 22: Simplified Access Rights Evaluation

    7 Simplified access rights evaluation The model of access rights contains time schedules and a table of holidays. A block diagram for access right evaluation can be seen on Pic. 5. READING ID (and PIN) ID FOUND Valid PIN or reader without PIN ACCESS DRIVEN BY TIME SCHED.
  • Page 23: Ids Control Function

    8 IDS control function The special function of the reader is a simple IDS control with a use of a WIO 22 relay module. The function description follows. 8.1 IDS connection IDS control function is performed by the second relay of the WIO 22 relay module, which...
  • Page 24: Ids General Notes

    Remote door open function cannot be performed when the IDS is armed – such attempt is stored in the events archive. • Permanent door lock release according to a time schedule function is performed only when the IDS is disarmed. 9 Useful links • Wiring diagrams: http://techfass.cz/diagrams-aps-mini-plus-en.html • Program equipment: http://techfass.cz/software-and-documentation-en.html Page 24...

This manual is also suitable for:

Aps mini mrep 78Aps mini mrep 78xAps mini mrep 78e

Table of Contents