2 Product Description NREM 76 reader modules are designed for connection to the APS BUS of the APS 400 identification system. Up to 64 reader modules NREM 76 can be connected to a single MCA 168 controller. The reader modules are available in various modifications differing in the way of usage. 2.1 NREM 76 module Reader module for general use designed for applications with remote antenna module, see Pic.1.
54476401 ✓ ✓ NREM 76.BTW – EM Bticino Light - White 54476601 Table 1: Product version – TECHFASS factory ID media reading; – EM Marin ID media reading; 3.2 Technical features 8 ÷ 15 VDC Supply voltage Typical 95 mA...
3.3 Special accessories AEM 12 51400300 Antenna module for hidden assembly (no buzzer or LED) AEM 12.1 51400301 Antenna module for hidden assembly (buzzer present, no LED) AEM 13 51400400 Antenna module with a ferrite coil for Targha panels WIO 22 51901200 Remote control module, 2x relay Table 3: Special accessories...
4 Installation 4.1 Terminals and jumpers ANT1 ANT2 Supply voltage +13,8 V BP + BP - Supply voltage 0 V Input 1 Input 2 150Ω BIAS A IO Port 3 BIAS B Alarm output Wiegand DATA 0 Wiegand DATA 1 A cable - RS 485 line B cable - RS 485 line Relay C...
4.2 Standard connection (recommended, not obligatory) Input 1 Door contact, active when door closed Request to exit button or handle contact, active when button or Input 2 handle pressed Output 1 Door lock control (relay) Output 2 AUX functions (transistor output +5 V/5mA) + yellow LED External tamper (Standard operating mode) I/O Port External reader buzzer control (op.
MCA 168 controller. Detailed instructions for setting reader module parameters are described in the APS 400 Network Reader configuration program user’s guide available at: http://www.techfass.cz/files/m_aps_400_network_reader_en.pdf. 6 Reader module functioning 6.1 Operating modes NREM 76...
WIEGAND data format IDs (more information in APS 400 Network Reader guide available at http://www.techfass.cz/files/m_aps_400_network_reader_en.pdf). 6.4 Wiegand interface configuration 6.4.1 Standard operating mode This is the module default operating mode. The Wiegand interface is used for controlling the WIO 22 module in this configuration.
(tamper signal = relay switched on) Table 14: Signal function in WIEGAND operating mode Since the FW version 2.79 the reading synchronization of a couple of TECHFASS readers is implemented, enabling to cancel the mutual disturbance of the modules. The reader module offers the...