MTU Detroit Diesel 12 V 2000 P62 Technical Publication page 84

Table of Contents

Advertisement

80
Fault
Alarm text
code
078
LIM
INTERCOOLER
LEV.
079
L Bin-EXTERN 3
080
L Bin-EXTERN 4
089
ENGINE SPEED
LOW
090
IDLE SPEED LOW
091
RUN UP SPEED
LOW
092
START SPEED
LOW
093
PREHEAT TEMP.
LIMIT2
094
PREHEAT TEMP.
LIMIT1
100
EDM NOT VALID
101
IDM NOT VALID
102
INVALID FUEL
CONS. 1
103
INVALID FUEL
CONS. 2
104
OP HOURS1 NOT
VALID
105
OP HOURS2 NOT
VALID
106
ERR REC1 NOT
VALID
107
ERR REC2 NOT
VALID
MS15009/00E 06-09
Meaning
Alarm from external charge-air
coolant level monitoring
Alarm from external binary
channel 3
Alarm from external binary
channel 4
Engine speed lower than 200
rpm;
automatic engine shutdown
Idle speed not reached within a
specified period;
Termination of starting procedure.
Run-up speed not reached within
a specified period;
Termination of starting procedure.
Starter speed not reached within
a specified period;
Termination of starting procedure.
Coolant preheating temperature
too low during starting (2nd limit)
Termination of starting procedure
(depending on project design)
Coolant preheating temperature
too low during starting (1st limit)
Check sum error of
measuring-point data in EDM
Check sum error of
measuring-point data in IDM
Check sum error of accumulated
fuel consumption data in EDM
(redundant data record 1)
Check sum error of accumulated
fuel consumption data in EDM
(redundant data record 2)
Check sum error of hour meter
data in EDM
Check sum error of hour meter
data in IDM
Check sum error of fault memory
in EDM (redundant data record 1)
Check sum error of fault memory
in EDM (redundant data record 2)
Task
(Depending on the corresponding measuring
point, which is read via CAN bus)
(Depending on the corresponding measuring
point, which is read via CAN bus)
(Depending on the corresponding measuring
point, which is read via CAN bus)
Re-start the engine (→ Page 51).
Note further alarms.
Note further alarms.
Note further alarms.
Check preheating pump / preheating system
(see manufacturer's documentation).
Check preheating pump / preheating system
(see manufacturer's documentation).
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
If fault occurs repeatedly: Contact Service.
Troubleshooting