Troubleshooting
Fault code
Fault message
384
TRAN.OUT4 PLANT
DEF
385
TRAN.OUT5 PLANT
DEF
386
TRAN.OUT6 PLANT
DEF
390
MCR EXCEEDED
392
L1 T-COOLANT RED
393
L2 T-COOLANT RED
394
L1 P-LUBE OIL RED
395
L2 P-LUBE OIL RED
396
TD COOLANT
397
TD OIL PRESSURE
MS15009/00E 06-09
Meaning
Binary transistor output TAA 4
faulty.
Binary transistor output TAA 5
faulty.
Binary transistor output TAA 6
faulty.
MCR violation
Redundant coolant
temperature (1st limit value).
Redundant coolant
temperature (2nd limit value).
Redundant lube oil pressure
(1st limit value).
Redundant lube oil pressure
(2nd limit value).
Transmitter deviation coolant
temperature.
Transmitter deviation engine
oil pressure.
Action
Check cabling to plant.
Check cabling to plant.
Check cabling to plant.
1. No action necessary if alarm only
signaled temporarily;
2. contact Service if alarm signaled
permanently.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.
1. Check cabling (→ Engine
operating instructions).
2. Contact Service
• Check sensor.