Superheat controller type EKD 316
EKD 316 – Parameter identification (modbus)
Explanations:
Parameter – The parameter name and abbreviation
PNU
– The Parameter Number.
Note: This is equivalent to the modbus register number (modbus address + 1)
R/W
– R means read only, RW means it can be changed
Config lock – If the parameter is config locked it means that the value can only be changed when the main switch is off
Min
– The minimum value of the parameter
Max
– The maximum value of the parameter
Default
– The default value of the parameter (factory setting)
Actual value – Values are read/written as 16 bit integer values without decimals. This is the default value as read via modbus
Scale
– This shows the scaling factor of the value. *1 means that there is no scaling. *10 means that the read value is 10 times larger than
the actual value.
Parameter
PNU
R/W
Config lock
Injection control (1)
n04 Kp factor
3003
R/W
n05 Tn seconds
3004
R/W
n06 Td seconds
3005
R/W
n09 Max SH
3015
R/W
n10 Min SH
3021
R/W
n11 MOP
3013
R/W
n15 Start time
3017
R/W
n17 MinOdAtStart
3012
R/W
n18 Stability
3014
R/W
n19 Kp min.
3024
R/W
n20 Kp T0
3025
R/W
n21 SH mode
3026
R/W
n22 SH close
3027
R/W
n32 ETS OD% Max
3023
R/W
n44 TnT0 sec.
3039
R/W
o56 Reg. type
2076
R/W
x
Motor(2)
n37 Max steps
3032
R/W
x
n38 Max StepsSec
3033
R/W
x
n39 Start backlash
3034
R/W
x
n40 Backlash
3035
R/W
x
n03 Valve type
3002
R/W
x
Alarm settings (3)
A34 Battery low
10035
R/W
Miscellaneous (11)
r05 Temp.unit
105
R/W
r09 Adjust S2
113
R/W
r10 Adjust S3
114
R/W
o20 MinTransPres
2034
R/W
o21 MaxTransPres
2033
R/W
o30 Refrigerant
2551
R/W
x
o18 Manual ctrl.
2075
R/W
o45 Manual OD%
2064
R/W
Service (12)
o61 Appl.mode
2077
R/W
x
u10 DI1 status
2002
R
u06 Analog input
2504
R
--- AL/Light rel
2509
R
--- Reset alarm
2046
R/W
--- Rfg.Fac.A1
2548
R/W
--- Rfg.Fac.A2
2549
R/W
--- Rfg.Fac.A3
2550
R/W
Alarms (13)
--- Standby
20000
R
--- EKC Error
20001
R
--- S2 Error
20002
R
--- S3 Error
20003
R
--- P
inp.error
20004
R
e
--- AI inp.error
20005
R
--- No Rfg. Sel.
20006
R
--- Battery low
20008
R
Danfoss only (14)
o03 Unit addr.
2008
R/W
x
No text (15)
r12 Main switch
117
R/W
u20 S2 temp.
2537
R
u21 Superheat
2536
R
u22 SuperheatRef
2535
R
u24 Opening %
2542
R
u25 EvapPress P
2543
R
e
u26 EvapTemp T
2544
R
e
u27 Temp. S3
2545
R
--- EKC State
2007
R
22
DKRCC.PS.RP0.A1.02/520H7142
Min
Max
Default
Actual value
Scale
0.5
20.0
2.0
20
*10
30
600
120
120
*1
0
90
0
0
*1
2.0
15.0
10.0
100
*10
1.0
12.0
6.0
60
*10
0.0
200.0
20.0
200
*10
1
90
0
0
*1
0
100
0
0
*1
0
10
5
5
*1
0.0
1.0
0.3
3
*10
0.0
10.0
0.4
4
*10
1
2
1
1
*1
1.0
15.0
4.0
40
*10
0
100
100
100
*1
10
120
30
30
*1
1
2
1
1
*1
10
999
262
262
*1
5
300
300
300
*1
0
100
10
10
*1
0
100
23
23
*1
0
8
1
1
*1
0
1
0
0
*1
0
1
0
0
*1
-10.0
10.0
0.0
0
x10
-10.0
10.0
0.0
0
x10
-1.0
0.0
0.0
0
*10
1.0
200.0
12.0
120
*10
0
37
0
0
*1
0
3
0
0
*1
0
100
0
0
*1
1
2
2
2
*1
0
1
0
0
*1
0.0
30.0
0.0
0.0
*10
0
1
0
0
*1
0
1
0
0
*1
8000
12000
10428
10428
*1
-4000
-1000
-2255
-2255
*1
1000
3000
2557
2557
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
0
1
0
0
*1
1
240
240
240
*1
0
1
0
0
*1
-200.0
200.0
0.0
0.0
*10
0.0
100.0
0.0
0.0
*10
0.0
100.0
0.0
0.0
*10
0
100
0
0
*1
-200.0
200.0
0.0
0.0
*10
-200.0
200.0
0.0
0.0
*10
-200.0
200.0
0.0
0.0
*10
0
100
0
0
*1
©Danfoss A/S (AC-MCI / sw), 2014-03
Manual
Superheat controller type EKD 316

Installation considerations

Accidental damage, poor installation, or site conditions can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, an incorrect installation, for example, could
still present problems. Electronic controls are no substitute for
normal, good engineering practice.

List of literature

www.danfoss.com
Click: "Technical literature" in the left bar
Click: Refrigeration and Air Conditioning " > Technical literature"
Paste or write the no. in the box " Literature No."
ƒ Catalogue RK0YG
ƒ ETS valves, technical brochure DKRCC.PD.VD
ƒ Installation guide for data communication RC8AC
Your local Danfoss agent will be pleased to assist with further
advice, etc.
©Danfoss A/S (AC-MCI / sw), 2014-03
DKRCC.PS.RP0.A1.02/520H7142
Danfoss will not be responsible for any goods, or plant
components, damaged as a result of the above defects. It is the
installer's responsibility to check the installation thoroughly, and
to fit the necessary safety devices.
Particular attention is drawn to the need for a "force closing" signal
to controllers in the event of compressor stoppage, and to the
requirement for suction line accumulators.
Your local Danfoss agent will be pleased to assist with further
advice, etc.
23