Superheat controller type EKD 316
Appendix I

Menu survey

Function
The menus from either column 1 or column 2 are shown
Normal display
During regulation the actual level of superheating is displayed.
(If you would like to see the expansion valve's actual opening degree, press the bottom button for
approx. one second.)
During control with an analogue signal the opening degree is displayed.
Reference
Units (0=°C+bar/1=°F+psig)
Correction of signal from S2
Correction of signal from S4
Start/stop of refrigeration
Alarm
Battery monitoring
Regulating parameters
Valve definition:
0 =
ETS 12.5, ETS 25, KVS 15
5 =
user-defined
1 =
ETS 50, CCM 10, CCM 20, CCM 30
6 =
Saginomiya UKV/SKV/VKV/PKV
2 =
ETS 100, CCM 40
7 =
ETS 6
3 =
ETS 250, KVS 42
8 =
CCMT 2, CCMT 4, CCMT 8
4 =
ETS 400
On using external display EEKA 164A, please check page 9 section ETS valve
P: Amplification factor Kp
o56 = 1; n04 = 2.0
o56 = 2; n04 = 0.7
:
(
Warning
Changes to n04 are lost when changing o56)
I: Integration time T
D: Differentiation time Td (0 = off )
Max. value of superheat reference
Min. value of superheat reference
MOP (max = off )
Signal reliability during startup. Safety time period.
Should only be changed by trained staff
Signal reliability during startup – opening degree's start value. Should only be changed by trained
staff.
Stability factor for superheat control.
Changes should only be made by trained staff
Damping of amplification around reference value
Changes should only be made by trained staff
Amplification factor for superheat
Changes should only be made by trained staff
o56 = 1; n20 = 0.4
o56 = 2; n20 = 3.0
Warning
:
(
Changes to n20 are lost when changing o56)
Definition of superheat control mode
1 = MSS,
2 = LOADAP
Value of min. superheat reference for loads under 10%
Max. opening degree
Changes should only be made by trained staff
Number of steps from 0-100% opening degree (only if n03 = 5 (User-defined))
:
Note
The display can only show three digits, but the setting value is four digits.
Only the three most important are shown, i.e. a reading of e.g. 250 means a setting of 2500. (Auto-
matic setting when valve is selected in n03).
Number of steps per second
Start backlash (extra closing steps at 0% opening (in % of n37))
Integration time for inner loop (TnT0)
Compensation for spindle play
16
DKRCC.PS.RP0.A1.02/520H7142
SW = 1.32
Fac.
Application
Parameter
Min.
Max.
set-
choice
ting
menu = o61
1
2
-
K
-
-
%
-
r05
0
1
0
r09
-10.0 K 10.0 K
0.0
r10
-10.0 K 10.0 K
0.0
r12
Off/0
On/1
Off/0
A34
Off/0
On/1
Off/0
n03
0
8
1
n04
0.5
20
2.0/0.7
n05
30 s
600 s
120
n06
0 s
90 s
0
n09
2 K
15 K
10
n10
1 K
12 K
6
n11
0.0 bar 200 bar 20
n15
0 sek.
90 sek
0
n17
0%
100%
0
n18
0
10
5
n19
0.0
1.0
0.3
n20
0.0
10.0
0.4/3.0
n21
1
2
1
n22
1 K
15 K
4
n32
0 %
100 %
100
10
990
n37
(100
(9990
262
stp)
stp)
300
n38
5 stp/s
300
stp/s
n39
0%
100%
10
n44
10 s
120 s
30
n40
0 stp
100 stp 23 stp
©Danfoss A/S (AC-MCI / sw), 2014-03
Manual
Superheat controller type EKD 316
Miscellaneous
Controller's address
If the valve's opening degree should be controlled with an external signal, the signal is defined as:
0: no signal
1: 0-20 mA
2: 4-20 mA
3: 0-10 V
4: 1-5 V
Manual control of outputs:
OFF: no manual control
1: Manual control with "o45" enabled
2: Simulate Alarm off : connection between 24 and 25
3: Simulate Alarm on : connection between 24 and 26
Working range for pressure transmitter – min. value
Working range for pressure transmitter – max. value
Refrigerant setting
1 = R12
6 = R13
11 = R114
16 = R401A
21 = R407A
26 = R600
2 = R22
7 = R13b1
12 = R142b
17 = R507
22 = R407B
27 = R600a
3 = R134a
8 = R23
13 = User def.
18 = R402A
23 = R410A
28 = R744
24 = R170
29 = R1270
4 = R502
9 = R500
14 = R32
19 = R404A
5 = R717
10 = R503
15 = R227
20 = R407C
25 = R290
30 = R417A
Manual control of the valve's opening degree. The function can only be operated if o18 has been set to
"1".
This function is only for manual operation. It must not be used for as a regulation function.
Selection of control mode:
1=Normal
2 = With inner loop (S media temperature less T0)
Application mode. Menus blanked out so only the shaded menus are seen. See the two columns to the
right.
1: Controlling a valve with an analogue signal
2: Superheat regulation
Service
Analog input (21-22)
Read status of input DI (20-21)
Temperature at S2 sensor
Superheat
Superheat reference
Read valve's opening degree
Read evaporating pressure
Read evaporating temperature
Temperature at S4 sensor
Configuration settings (n03, n37, n38, n39, n40, o03, o30, o56 and o61) available only when regulation is stopped (r12=off ).
Factory settings are indicated for standard unit (see code number, page 1). Other code number have customised settings.
Valve overview
n03
Valve type
n37
n38
0
ETS 12½, ETS 25, KVS 15
262
300
1
ETS 50, CCM 10, CCM 20, CCM30
262
300
2
ETS 100, CCM 40
353
300
3
ETS 250, KVS 42
381
300
4
ETS 400
381
300
5
-
6
Saginomiya
24
30
7
ETS 6
24
30
8
CCMT 2, CCMT 4, CCMT 8
110
300
©Danfoss A/S (AC-MCI / sw), 2014-03
DKRCC.PS.RP0.A1.02/520H7142
o03
0
240
240
o10
0
4
0
o18
off/0
3
Off /0
o20
-1 bar
0 bar
-1.0
o21
1 bar
200 bar 12.0
31 = R422A
R36 =
32 = R413A
Opteon XP10
o30
0
37
0
33 = R422D
37 = R407F
34 = 427A
35 = R438A
o45
0 %
100 %
0
o56
1
2
1
o61
1
2
2
1
u06
mA (V)
u10
on/off
u20
°C
u21
K
u22
K
u24
%
u25
bar
u26
°C
u27
°C
2
17