Profinet Controller Configuration; Backward Com Patibility With Cpu320/Cru320/Cpu315 - Emerson PACSystems RX3i IC695CPE330 Quick Start Manual

Table of Contents

Advertisement

To enable redundancy in a CPE330 project, select the CPE330 target in the
PME Navigator and use the Property Inspector to change the Enable
Redundancy target property to True.

PROFINET Controller Configuration

PAC Machine Edition 8.60 SIM 13, PME 9.00 SIM 4 or later may be used to
configure an Embedded PROFINET Controller in the CPE330 Hardware
Configuration on LAN 2.
To enable the PROFINET Controller in a CPE330 project, select the CPE330
2
target in the PME Navigator and open the Hardware Configuration. On the
Settings tab, change the LAN 2 Mode to PROFINET. The PROFINET Controller
node description now displays that it is using LAN 2 as a submodule under
the CPE330.
Compatibility with CPU320/CRU320/CPU315
The CPE330 also serves as a drop-in replacement for the CPU320, CRU320,
and CPU315 Controllers without the need to upgrade PME. To download
projects intended for the CPU320/CRU320 to a CPE330 with versions of
PME that do not support the CPE330, you must change the CPE330's
compatibility setting.
2
CPE330 release 8.90 or later is required for the embedded PNC feature.
18
PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide
GFK-2941K

Advertisement

Table of Contents
loading

Table of Contents