Emerson PACSystems RX3i IC695CPE330 Quick Start Manual page 5

Table of Contents

Advertisement

and faster are possible with 16 or fewer devices. When there are more than
16 devices configured, update rates of 16 ms and higher are available.
Supports the Remote Get HART
allows the user application to read information from a HART device
connected to an RX3i Analog module in an IC695PNS001 RX3i PROFINET
Scanner. A UDFB that automates the COMMREQ control logic is available for
download. (Refer to New Features and Enhancements for additional
information.)
Configured with Sequence of Events recording through the Embedded
PROFINET Controller when used with up to four IC695PNS101 Advanced
PROFINET Scanner modules. A RX3i SoE system supports events from up to
512 SoE input points with a system storage buffer for up to 128,000 events at
a maximum rate of 400 events per second per PNS101. Each PNS101
supports SoE recording with IRIG B time synchronization of events accurate
to 1ms and buffers up to 4000 events from up to four IC694MDL660
32 Circuit Discrete Input modules. Unmodulated IRIG B time signals are
decoded by the PNS101 using either an IC695HSC304 or IC695HSC308 High
Speed Counter Module. SoE recording is available in both simplex and
redundant PROFINET systems.
Supports programming in Ladder Diagram, Structured Text, Function Block
Diagram, or C.
Contains 64 Mbytes of configurable data and program memory.
Supports auto-located Symbolic Variables that can use any amount of user
memory.
4
PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide
®
Device Information COMMREQ, which
GFK-2941K

Advertisement

Table of Contents
loading