Planning and Commissioning Manual
Deactivation
To deactivate the pulse counter function, follow this step:
 Turn DIP switch 4 to "OFF".
An alarm is activated after one pulse count.
DIP Switch Setting
9.7

Directional Detection

(Models PRO-45D, PRO-45DH only)
This function enables monitoring of a detection area in particular directions to reduce false
alarms and improve the performance of the detector. Movement from left to right and right to
left can be recognized. Moreover, in software operation bi-directional detection can be set.
DIP Switch settings
To change directional detection:
 Set DIP switch 4 to "ON".
Bi-Directional Detection
To activate the bi-directional detection, follow these steps:
1.
Set DIP switches 1 and 2 to "ON" to change to software mode,
2.
Open the "Setting" menu,
3.
Choose "Bi-directional" from the drop-down menu "SW Directional detection".
9.8

Mounting Height Adjustment

PRO-51, PRO-85, PRO-85H, PRO-100, PRO-100H, PRO-250H only
The mounting height feature allows the adjustment of the detector´s sensitivity in relation to
the mounting height. This feature is available for long-range detectors only.
DIP Switch Position
40
ADPRO Passive-Infrared (PIR) PRO Series by Xtralis
DIP-Switch
4
NOTE!
DIP switch 4 is only used in models (PRO-45D and PRO-45DH) for
directional detection.
For volume models (PRO-18, PRO-18H, PRO-30, PRO-40, PRO-51,
PRO-85, PRO-85H) DIP switch 4 is used for the impulse counter.
On other models DIP switch 4 has no function.
DIP-Switch
4
4
ON
DIP Switch
7
7
OFF
Status
Function
OFF
Pulse counter
Status
Function
OFF
from left to right
from right to left
Status
Function
ON
Higher > 3 m (10 ft.)
Lower < 3 m (10 ft.)
Doc. 20780_03