Fixation
If the desired performance is reached:
1.
Fix the aligned detector horizontally with a nut underneath.
2.
Fix the aligned detector vertically with a nut on the right side.
After the test
1.
Remove the cable strap,
2.
Open the cover,
3.
Unplug the CT-PRO transmitter,
4.
Reconnect the RS-485 plug:
5.
Close the housing tightly with both screws.
The alignment is concluded.
8.1.5 Walk Test – Software Operation
Performing walk test using ADPRO Windows® software:
1.
Install the software (for installation instructions, see chapter 10),
2.
Open the cover of the detector,
3.
Connect the detector to a PC via an RS-485 connection, either through the RJ12 test
socket or the A/B lines (see diagram in chapter 13.2),
4.
Set DIP switch 1 and DIP switch 2 to "ON":
34
ADPRO Passive-Infrared (PIR) PRO Series by Xtralis
(51/85/100/250)
NOTES!
Be careful NOT to change the aligned position of the detector.
Doc. 20780_03