5.3

Modes of operation

The table below gives an overview of the available operation modes, link speed, number
of signals, data sampling time and typical devices:
Link speed
Max. number of signals
per FO link
Single fiber input-only modes
2Mbit
32 INT + 32 Digital
3Mbit
64 INT + 64 Digital
64 REAL + 64 Digital
5Mbit
8 INT + 8 Digital
32Mbit
64 INT + 64 Digital
128 INT + 128 Digital
512 REAL + 512 Digital
DPM-S mode
8 x (64 INT + 64 Digital)
Bidirectional fiber modes (output link required)
5Mbit
8 INT + 8 Digital
32Mbit Flex
variable*
Single fiber output-only modes (output link required)
3Mbit
64 REAL + 64 Digital
32Mbit
Not supported by PC software yet
*Example: payload transmission of 64 Byte at 25 µs sampling time or 3100 Byte at 1 ms.
Manual
Sampling time
≥1 ms
≥1 ms
≥1 ms
≥50 µs
≥50 µs
≥100 µs
≥800 µs
≥800 µs
≥1 ms
≥40 µs
≥10 µs
≥1 ms
Issue 1.11
Typical device
ibaPADU16/32
(old, S/N < 1000)
ibaPADU8/16/32
ibaLink-SM-64-i-o
SIMATIC TDC LO5
SIMATIC TDC LO6
SIMATIC TDC LO6
ABB AC 800PEC (1 ms)
ibaBM-DPM-S (1 ms)
ibaBM-COL-8i-o (1 ms)
ibaPADU-8-M
ibaPADU-8-ICP
ibaPADU-S-CM
ibaNet750BM