3.3.3
3.3.4
3.3.5
21/1531-ASP11301 Uen C 2017-03-28
Note: Do not cut the cables. The shortest length of the cables from the AC/DC unit to
the DC/DC board must be 5 meters.
CONNECTING AC/DC-UNIT 51305282 TO THE MAINS
The Power Unit have IEC connector on the rear side. Connect the mains cables and
secure them to avoid power breakdown.
CONNECTING AC/DC TO THE LAN
The Power Unit 51305282 can be equipped with a communication module, the PCC
Unit, 5130283. This unit communicate via the LAN. For details about functionality and
configuration, see suppliers data sheet/manual.
CONNECTING POWER (-48V) TO FAN UNIT BFD50908/4
Two types of cables can be used to Power the Fan Unit. Single cables or Splitter
cables.
Single Cables: Connect the Power to the fan unit using cable 51305286, 5 meter long
or 51305287, 12 meters long, see item (1) in Fig. see Figure 13: Single cables to the
Fan Unit BFD50908/4 and to 7U chassis on page 21.
Splitter cables: Connect the Power to the fan unit using cable 50006938, 5 meter long
or 50006937, 12 meters long, see item (1) in Fig. see Figure 14: Splitter Cable to the
Fan Unit BFD50908/4 and to 7U chassis on page 21
Note: If Alarm handling is required, cables marked with *) are also needed. For alarm
cables and plugs, see 5.4.2 MiVoice MX-ONE Classic with Power Unit on page
46.
Note: If only one Power cable is connected to the Fan Unit, the alarm on the Fan will
be activated. This is not possible to re-configure. To avoid the alarm in the Fan,
feed the Fan unit with 2pcs of Power cables or use the Splitter cables.
C
ABLING
20