Power Terminals; Remote Keypad Mounting - Toshiba TE-18-BP Quick Start Up Manual

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
 

Power Terminals:

Connection points are bus tabs with pre-drilled holes (see below). Use appropriate compression or
mechanical lugs for termination to these bus tabs.
Suggested wire sizes and tightening torques for factory-supplied connectors for conductors rated for 75C are
shown in the chart below. Always consult local codes and industry standard practices for proper wires sizes to
accommodate voltage drop and ambient conditions.
Model
Number
TE-18-BP
TE-28-BP
TE-39-BP
TE-48-BP
TE-62-BP
TE-78-BP
TE-92-BP
TE-112-BP
TE-150-BP
TE-160-BP
TE-210-BP
TE-275-BP
TE-361-BP
TE-450-BP
TE-550-BP
TE-600-BP
TE-862-BP
TE-900-BP
TE-1006-BP
TE-1250-BP
Table 3: TE Series Wire Ranges and Torque Specifications. Note: TBD = To Be Determined at a later
date. 

Remote Keypad Mounting

The keypad / operator interface unit can be remotely mounted up to 10' (3 meters) away from the starter, i.e.
on the enclosure door. A remote mounting kit is necessary, which consists of an adaptor plate, a doorframe
for NEMA 12 enclosures and a pre-assembled ribbon cable available in 1-meter length increments. Detailed
assembly instructions and an enclosure cutout template are included with the kit. See Industrial Catalog for
part numbers of the available kits.
Figure 4
Remote Keypad Mounting
Kit Components
12 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Suggested
Current Range
Wire Size
Min.- Max.
AWG
9 - 18
12
14 - 28
10
19 - 39
8
24 - 48
6
36 - 62
4
39 - 78
3
46 - 92
2
56 - 112
2
75 - 150
0
80 - 160
2/0
105 - 210
4/0
137 - 275
300 kCMIL
180 - 361
500 kCMIL
225 - 450
2 x 250 kCMIL
275 - 550
2 x 250 kCMIL
300 – 600
TBD
431 – 862
TBD
450 – 900
TBD
503 - 1006
TBD
625 - 1250
TBD
Tightening
Screw /
Torque
Bolt Size
in.-lbs.
1 x M5
35
(included)
1 x M8
45
(included)
1 x M8
80
(included)
1 x 0.38" hole
(M10)
200
for User supplied
lugs
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
Type 12
Door Frame
Ribbon Cable ,
1, 2 or 3 Meters
(3.28, 6.56 or 9.84')
Tightening
Suggested
Torque
Wire Size
2
Nm
ISOmm
6
10
4
16
16
25
35
5
35
50
70
9
70
120
150
15
300
2 x 150
2 x 150
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
Adaptor Plate
TE Starter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents