4 FUNCTIONS

4.4 Handy Functions

4.4.1 Simplifying the initialization procedure registration of remote device stations (Remote
device station initialization procedure registration function)
4 - 44
This section explains some handy functions of the QJ61BT11.
The initial settings of remote device stations, which in previous models were done
using the sequence program, can now be performed using the GX Developer for
registration to the PLC CPU.
Settings such as "A-D conversion enable/disable" and "Averaging processing
specification" can be performed easily with the AJ65BT-64AD.
For an example of an initialization procedure using the GX Developer, see Section
10.3.
(1) Initialization procedure setting method
The initial settings are performed using the "Remote device station initial" in the
network parameters. A maximum of 16 stations can be set. When 17 or more
remote device stations are connected, perform the initial settings for the 17th and
subsequent stations using the sequence program.
(a) In "Target", set the station number of a module for which the initial settings
are to be performed.
Setting range: 1 to 64
(b) Set the initialization procedure in "Regist procedure".
1) Input format
Set the data input format for "Write data" in details of execution.
Setting range: DEC.
Default:
HEX.
DEC.
MELSEC-Q
4 - 44