6 PARAMETER SETTINGS

6.4 Example of Parameter Setting with Dedicated Instruction

6 - 16
This section explains the parameter setting with the RLPASET instruction. For more
details on the GX Developer operation, refer to the GX Developer Operational Manual.
The explanations in this section are based on the following example of the system
configuration.
Station number 1
Local
Master
station
station
(occupies
(X/Y00 to 1F)
1 station)
POINT
(1) The remote I/O net mode cannot be used.
The module operates in remote net mode.
(2) It is not possible to set input status from a data link faulty station.
Inputs from a data link faulty station are cleared.
(3) The standby master function is not available.
(4) Do not use GX Developer for setting the network parameters, if the network
parameters of all the modules are set by the RLPASET instruction.
Change the "No. of boards in" setting to blank if the network parameters have
been already set by GX Developer.
Moreover, in case a system includes both a module for which the network
parameters are set by GX Developer and a module for which the network
parameters are set by the RLPASET instruction, the module for which the
network parameters are set by the RLPASET instruction should not be
included in the "No. of boards in" setting of GX Developer.
(5) When switching the PLC CPU from RUN to STOP, output to the RY of the
master station, remote station, local station, intelligent station, and standby
station are held.
(1) PLC parameter setting
Station number 2
Station number 3
Remote I/O station
Remote I/O station
(Error invalid station)
(Reserved station)
(occupies 1 station)
(occupies 1 station)
(a) I/O assignment setting screen
Set the following for the slot in which the master
module is mounted.
The type setting is required; set other items as
needed.
Type
Model name
Points
Start XY
MELSEC-Q
: Select "intelli."
: Enter the module model name.
: Select 32 points
: Enter the start I/O number for
the master module.
6 - 16

Advertisement

Table of Contents
loading