Bacnet Points List For Bfc Firmware V3.1.0 - Price BFC Series Manual

Flow controller for fan filter units
Hide thumbs Also See for BFC Series:
Table of Contents

Advertisement

BACNet Flow CoNtroller
MAINTENANCE
MAINTENANCE

BACnet points list for BFC firmware v3.1.0

Object
Name
Analog Input 1
AI1
(BAS)
Analog Input 2
AI2
(LED)
AI3
Thermistor
AI4
ECM Speed
AI5
Unit Pressure
BI1
Contact Closure
Analog Output 1
AO1
Filter Load
Analog Output 2
AO2
Unit Pressure
Analog Output 3
AO3
(BAS)
AO4
ECM Setpoint
AV1
Filter Load
AV2
Filter Runtime
AV3
Motor Runtime
AV4
Airflow
Filter Calibrated
AV5
Pressure
Filter Trip
AV6
Pressure
Filter Loading Trip
AV7
Point
28
BACNet FLow CoNtroLLer - Manual | priceindustries.com
Units
Default
Range
Volts DC Dynamic
Dynamic
Volts DC Dynamic
Dynamic
°F°/°C
Dynamic (-59)-300
r/min
Dynamic
0-2500
in. w.g.
Dynamic
Dynamic
Contacts
Contacts
Open/
Dynamic
Open/
Closed
Closed
0-10
Volts DC
N/A
VDC
0-10
Volts DC
N/A
VDC
0-10
Volts DC
N/A
VDC
%
50
0-100
%
0
0-100%
Hours
N/A
0-99999
Hours
N/A
0-99999
Cfm
N/A
0-9999
in. w.g.
N/A
Dynamic
in. w.g.
0
Dynamic
Numeric
1.5
1-3
Description
0-10 VDC Signal for remote fan speed control
0-10 VDC Signal for remote LED dimming
(Only for UFFU w/ BACnet Dimming option)
Current air temperature over filter
Current RPM of motor
Current differential pressure measured
across the filter
Binary Input for monitoring only
Configurable for Unit Pressure, CFM, RPM,
Filter Load , BAS, *LED Dimming, *LED On/
Off (*for UFFU w/ BACnet Dimming)
Configurable for Unit Pressure, CFM, RPM,
Filter Load , BAS, *LED Dimming, *LED On/
Off (*for UFFU w/ BACnet Dimming)
Configurable for Unit Pressure, CFM, RPM,
Filter Load , BAS, *LED Dimming, *LED On/
Off (*for UFFU w/ BACnet Dimming)
Set ECM motor setpoint
Current percent of filter loading based on
new, clean filter pressure drop
Current number of hours on filter since last
reset. Enter value of zero after filter has
been replaced and calibrated.
Current number of hours on motor since
last reset
Current airflow
Unit pressure when filter was calibrated
Filter trip pressure
Set filter loading trip point
RETAINED
R/W
ON POWER
FAILURE
R
N
R
N
R
N
R
N
R
N
R
N
R/W
Y
R/W
Y
R/W
Y
R/W
Y
R
N
R/W
Y
R
N
R
N
R
N
R
N
R/W
Y