Service Menu - I/O - Price BFC Series Manual

Flow controller for fan filter units
Hide thumbs Also See for BFC Series:
Table of Contents

Advertisement

BACNet Flow CoNtroller
DISPLAY NAVIGATION
Service Menu – I/o
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through.
BAS (AI1)
0 VDC
AI2 (BAS leD)
0 VDC
CoNtACt CloSUre
Ao1 USAGe
FIlter loAD (DeFAUlt)
Ao1 PreSVAl
0 VDC
Ao2 USAGe
UNIt PreSSUre
(DeFAUlt)
Ao2 PreSVAl
0 VDC
Ao3 USAGe
BAS (DeFAUlt)
Ao3 PreSVAl
0 VDC
PreSS MeNU
to eXIt
8
BACNet FLow CoNtroLLer - Manual | priceindustries.com
Read Only – Displays current input BAS voltage for motor speed control
Read Only – Displays input voltage to Analog Input 2 for LED control (UFFU w/ BACnet Dimming Control only)
Displays current state of binary contacts used for night setback / secondary ECM setpoint (open / closed)
Configure Analog Output 1 for:
Unit Press - Unit Pressure; Range (0 in. w.g. to 2 in.w.g.)
CFM - Airflow; Range (0 - 5000 CFM)
RPM - Range (0 - 2500 RPM). See page 11 for RPM details.
Filter Load - Range (0 - 100%)
BAS - 0-10VDC signal to BAS
LED Dimming (0 - 100%)
LED On/Off (Changes autonomously Based on LED Dimming value)
Disabled
Read Only - Present Value for Analog Output 1
Configure Analog Output 2 same as AO1 options shown above.
Read Only - Present Value for Analog Output 2
Configure Analog Output 3, same as AO1 options shown above.
Read Only - Present Value for Analog Output 3