BACNet Flow CoNtroller
DISPLAY NAVIGATION
Service Menu – Fan
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through.
CUrreNt CFM
XXXX CFM
UNIt StYle
UNIt SIZe
2X2
wHeel tYPe
XXX
VoltAGe tYPe
XXX
Motor ProGrAM
XXX
Motor rUNtIMe
0 HrS
reSet Motor
rUNtIMe
CFM oFFSet
0 CFM
CFM tweAK
100 %
eCM SetBACK
PreSS MeNU
to eXIt
6
BACNet FLow CoNtroLLer - Manual | priceindustries.com
Read Only
Supply, Exhaust, CARES
Note:
Must match actual configuration of FFU
Displays the ECM motor calibration for FFU nominal size (2x2)
Selectable sizes are: 2' x 2', 2' x 3', 2' x 4'
Note:
Must match actual configuration of FFU.
Adjust unit wheel type from FC to BC. Read only varying on fan type and unit size
The wheel type is factory set, but it can be adjusted only under the Constant Torque setting. From there, you can set the
wheel type to BC on 2' x 3' and 2' x 4' units only.
Note:
BC wheel type is for Constant Torque only.
Adjust unit voltage type from 115/240/277.
Adjust fan type from Constant Volume to Constant Torque. Airflow (CFM) will be hidden if fan type is constant torque
Read Only – Displays number of hours on motor since last reset
Resets Motor Runtime
Adjust airflow reading +/- up to 500 CFM to coincide with balancer measured airflow
Example: flow hood reads 550 CFM
Airflow reading on BFC is 500 cfm
Adjust CFM offset to +50 CFM
Adjust airflow reading between 50 to 200%
Example: flow hood reads 550 CFM
Airflow reading on BFC is 500 cfm
Adjust CFM tweak to +110%
Secondary setpoint for use in turndown or night setback applications. This is activated upon contact closure.