Service Menu - Filter - Price BFC Series Manual

Flow controller for fan filter units
Hide thumbs Also See for BFC Series:
Table of Contents

Advertisement

BACNet Flow CoNtroller
DISPLAY NAVIGATION
Service Menu – Filter
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through.
FIlter tYPe
XXX
FIlter loAD
XX %
loAD trIP
1.50
FIlter rUNtIMe
0 HrS
reSet
FIlter
PreSS MeNU
to eXIt
Adjust filter type, BTR, RSR.
BTR = Bench Top Removable RSR = Room Side Removable
Read Only - Displays % of filter loading based on new, clean filter pressure drop
This represents the ratio between clean and loaded filter pressure. It is factory set for 1.5 times the clean filter pressure.
Example: If the filter calibrated pressure is 0.16 in. w.g., the loaded filter pressure will be 0.24 in. w.g.
Read Only – Displays number of hours on filter since last reset
Resets Filter Runtime.
Activate this to calibrate filter pressure during initial setup or filter replacement.
priceindustries.com | BACNet FLow CoNtroLLer - Manual
7