Mitsubishi Electric 800 Series Function Manual page 40

Cc-link ie tsn communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(N) Operation via communication and its settings
 Programming example for setting the operation commands
The following program gives a forward command and middle speed command to station 1 inverter
SW0B0.0
SB49
0
M0
X20
3
7
Y100F
b15
0
0
0
0
Run command
b0 : Forward rotation command
b1 : Reverse rotation command
b2 : High-speed operation command (RH)
b3 : Middle-speed operation command (RM)
b4 : Low-speed operation command (RL)
b5 : Jog operation selection (JOG)

These signals are initial values. You can change input signals using Pr. 180 to Pr. 189 (input terminal function selection).
Note that some of the signals do not receive a command from the programmable controller depending on the setting.
(Refer to the Instruction Manual (Detailed) of the inverter for the details.)
 Programming example for monitoring the output frequency
The following explains a program to read monitor functions of the inverter.
The following program reads the output frequency of station 1 inverter to D1.
Output frequency read code: H0001 (hexadecimal)
For the monitor codes, refer to
(Example) The output frequency of 60 Hz is indicated as H1770 (6000).
SB49
SW0B0.0
0
M0
X20
3
11
40
PARAMETER
b7
0
0
0
0
0
0
0
0
[Run command]
Middle speed
b6 : Second function selection (RT)
b7 : Terminal 4 input selection (AU)
∗1
b8 : Selection of automatic restart after instantaneous power failure (CS)
∗1
b9 : Output stop (MRS)
∗1
b10 : Start self-holding selection (STOP)
b11 : Inverter reset (RES)
∗1
page
35.
X1020
M0
Check the data link status of the station 1
Y1000
Forward rotation command (RY00)
Y1003
Middle speed operation command (RY03)
END
Y1000
b0
1
0
0
1
RY3F to RY00
1: ON
Forward rotation
0: OFF
∗1
∗1
∗1
∗1
M0
Check the data link status of the station 1
Set monitor code (H01) of output frequency
MOV H1
W126
to RWw26.
Turn on the monitor command (RY20)
Y1020
Read output frequency (RWr26) to D1
MOV W26 D1
when the monitoring (RX20) turns on.
END
One station
∗1
∗1