Mitsubishi Electric 800 Series Function Manual page 20

Cc-link ie tsn communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(N) Operation via communication and its settings
2.3.2
Initial settings for CC-Link IE TSN
communication
Use the following parameters to perform required settings for CC-Link IE TSN communication between the inverter and
other devices.
To make communication between other devices and the inverter, perform the initial settings of the inverter parameters
to match the communication specifications of the devices. Data communication cannot be made if the initial settings are
not made or if there is any setting error.
Pr.
Name
434
IP address 1
N700

435
IP address 2
N701

436
IP address 3
N702

437
IP address 4
N703

438
Subnet mask 1
N710

439
Subnet mask 2
N711

440
Subnet mask 3
N712

441
Subnet mask 4
N713

1130
Link speed selection
N741

1442
IP filter address 1 (Ethernet)
N760

1443
IP filter address 2 (Ethernet)
N761

1444
IP filter address 3 (Ethernet)
N762

1445
IP filter address 4 (Ethernet)
N763

1446
IP filter address 2 range
N764
specification (Ethernet)

1447
IP filter address 3 range
N765
specification (Ethernet)

1448
IP filter address 4 range
N766
specification (Ethernet)


The setting is applied after an inverter reset or power-ON.

The initial value after all parameters have been cleared.
IP address setting
For CC-Link IE TSN communication, the IP address of the inverter is set using the rotary switches on the CC-Link IE TSN
communication circuit board or inverter parameters. Note that the rotary switch setting has a higher priority than the
parameter setting (when the rotary switch settings are "1 to 254").
For CC-Link IE TSN communication, the third octet of the inverter's IP address is used as the network No. and the fourth octet
is used as the station number. (Enter the IP address assigned by the network administrator.)
20
PARAMETER
Initial value
Setting range
0 (192
)

0 (168
)

0 to 255
0 (50
)

0 (2
)

0 (255
)

0 (255
)

0 to 255
0 (255
)

0
0
0, 1
0
0
0 to 255
0
0
9999
9999
0 to 255, 9999
9999
Description
Enter the IP address of the inverter to be
connected to CC-Link IE TSN.
Enter the subnet mask of the network to which the
inverter belongs.
Set the communication speed.
Set the range of connectable IP addresses for the
network devices.
(When Pr.1442 to Pr.1445 = "0 (initial value)", the
function is invalid.)