Phoenix Contact Axioline F AXC Series User Manual page 21

Diagnostic registers, and error messges
Table of Contents

Advertisement

Table 2-1
Error codes for user errors [...]
Code
Additional code
(hex)
0B01
0B02
0B03
0B04
0B05
0B06
0B07
0B0C
OBC1
0BDE
8663_en_03
Meaning
A hardware or firmware error occurred.
A hardware or firmware error occurred.
A hardware or firmware error occurred.
A hardware or firmware error occurred.
Invalid parameters
Access not supported. (E.g., write protection)
Object does not exist.
A hardware or firmware error occurred.
Supply voltage not available for the local bus. Too many
devices connected or the higher-level power supply unit
is too weak.
Synchronization failed. Trigger signal does not corre-
spond to the specification.
Error codes
Remedy
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Check the parameters.
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Use a suitable power supply
unit.
Check the power consump-
tion of the devices; if re-
quired, use a power module
for communications power or
install a further Axioline F sta-
tion.
Check the synchronization
signal of the higher-level sys-
tem. Make sure that the cycle
time specification is properly
selected.
PHOENIX CONTACT
21

Advertisement

Table of Contents
loading