Error codes for user errors [...]
Code
Additional code
(hex)
0A0D
0A18
Invalid Used_Attri-
butes parameter
0A19
Number of bus devices The end of the frame was exceeded when accessing the
0 A1 A
Invalid Frame_Refer-
ence (if specified)
0A1C
Number of connected
devices
0A2F
0A51
0A54
0A60
0A70
0A73
Device number
0A74
Device number
0A75
Device number
0A76
Device number
0A77
Device number
0A7 A
0A7B
0A7C
0A81
Object index
8663_en_03
Meaning
A firmware error occurred.
A reserved bit is set in Used_Attributes.
configuration or line 0 was accessed.
The frame reference specified for the service does not
exist.
Maximum number of devices exceeded.
Number of devices is zero.
A frame reference from 1 to 254 is permitted only.
The maximum number of I/O points was exceeded.
No configuration frames could be assigned.
A reserved bit has been set in the Diag_Info attribute.
Device present with a chip version in the local bus that is
not supported.
Device of a manufacturer that is not supported present in
the local bus.
Device is indicating a serious error (e. g., faulty EE-
PROM).
The topology used by the device is not supported by the
master.
Error at the interface.
Invalid Dev_Type specified during loading.
Invalid Dev_ID specified during loading.
Invalid Dev_Length specified during loading.
Service (e.g, Create_Configuration) could not be exe-
cuted due to PDI communication malfunctions (timeout).
Error codes
Remedy
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Check the parameters.
Check the access.
Check the parameters.
Reduce the bus configura-
tion.
Connect the device and
check the connection.
Currently, the value 1 is per-
mitted only.
Reduce the number of I/O
points to the maximum num-
ber.
To obtain the exact number,
please refer to the documen-
tation for your controller.
Create the configuration
frame.
Check the parameters.
Replace the device.
Replace the device.
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Replace the device.
Check the connection be-
tween the electronics module
and bus base module.
Check the parameters.
Check the parameters.
Check the parameters.
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.