Installation
(2)
2....10 V DC
Control range of the steady control signal.
(3)
Setting of the travel direction with a control volt-
age of 10 V DC
Travel direction and
position feedback
100...0 %
(4)
Equal percentage
characteristic line
(5)
Free
When switching switch 6, the stored data for
valve adaptation will be deleted and a new ini-
tialisation run will be triggered.
During operation, an initialisation run will be
(6)
triggered automatically every 7 days, if no upper
or lower stroke position is approached during
this period.
The LED will flash green during initialisation.
5.4

Connection of the power supply

NOTICE
Damage to the actuator due to operation
in unmounted state
The actuator can be damaged and its func-
tion be impaired when operating the actuator
electrically without valve.
f The actuator must only be connected to
the power supply after installation.
NOTICE
Damage to the control technology due to a
high peak load when switching the actua-
tor on
f Use switching components which are
designed for a short-term peak load of up
to 12 A.
f Completely disconnect the power supply.
f Carry out the desired assignment (see Illust. 5 to
Illust. 7).
8
0.....10 V DC
Travel direction and po-
sition feedback 0....100
%
Linear characteristic
line
Electromotive actuator 24 V
f Connect the power supply.
Z After having connected the power supply for the
first time, the actuator will carry out an initialisation
run.
The product will be ready for operation after initiali-
sation.
Z Protect the stroke position indicator by turning the
dust cover (position (2) in Illust. 2) around by 180°.
5.4.1

Steady control

1 2 3 4 5
BU
Illust. 5: Pin assignment for steady control
(1)
0 V AC/DC
(2)
24 V AC/DC
(3)
Y = 0/2..10 V DC
(4)
Position feedback
0 V DC
(5)
Position feedback
0..10 V DC
5.4.2

3 point control

1
BU
Illust. 6: Pin assignment for 3 point control
(1)
0 V AC/DC
(2)
0 V or 24 V AC/DC
(3)
0 V or 24V AC/DC
The travel direction can be reversed by swap-
ping the supply lines to terminal 2 and 3 at the
actuator.
BN
GY
YE
GN
U = 0..10 V DC
0 V DC
Y = 0/2..10 V DC
24 V AC/DC
0 V AC/DC
blue (BU)
brown (BN)
grey (GY)
yellow (YE)
green (GN)
2 3
BN
GY
24 V AC/DC
0 V AC/DC
blue (BU)
brown (BN)
grey (GY)
115801283-V01.01.2020