Transport And Storage; Installation; Initial Installation; 5.2 Commissioning - oventrop Aktor M ST Operating Instructions Manual

Electromotive actuator 24 v
Table of Contents

Advertisement

Electromotive actuator 24 V
Protection class
IP54
Protective system
III according to EN 60730
Installation posi-
360°
tion
Weight
320 g
4.

Transport and storage

Temperature
-0 °C - 50 °C
range
Relative
0 - 85 %, not condensing
air humidity
Particles
Store dry and free from dust
Mechanical influ-
Protected from mechanical
ences
agitation
Weather influenc-
Do not store outdoors
es
Protect from direct sunlight
Chemical influ-
Do not store together with
aggressive fluids
ences
5.

Installation

5.1

Initial installation

Make sure that there is enough space for the
installation of the actuator.
CAUTION
Risk of burns due to hot components
An unprotected contact with hot components
may lead to burns.
f Wear safety gloves.
Illust. 3: Installation position
115801283-V01.01.2020
1. Fit the adapter set to your valve according to the
enclosed installation instructions.
2. Fit the actuator to the connection thread of the
adapter.
3. Hand tighten the collar nut.
Avoid cross threading.
NOTICE
Damage to the actuator when tightening
the collar nut with excessive torque
The actuator can be damaged and its
be function impaired if the collar nut is
over-tightened.
f Hand tighten the collar nut.

5.2 Commissioning

5.3

Configuration of the DIP switches

f Remove the casing cover.
f Configure the DIP switches.
Illust. 4: DIP switches
ON
(1)
Valve anti-blocking
function ON
If installation conditions allow, the valve an-
ti-blocking function can be activated during
commissioning.
The valve anti-blocking function will prevent
sticking of the stem if the valve is not activated
over a longer period, e.g. during the summer
break of heating systems.
If the valve anti-blocking function is activated,
the stem will be moved for a few seconds, if no
stroke lift is carried out within 10 days.
It is not possible to use the
valve anti-blocking function
during 3 point control!
Transport and storage
OFF
Valve anti-blocking
function
OFF
6
5
4
3
2
1
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aktor m 2pAktor m 3p l

Table of Contents