Commissioning; Configuration Of The Dip Switches; Connection Of The Power Supply; Steady Control - oventrop Aktor M ST L Operating Instructions Manual

Electromotive actuator, 24 v
Hide thumbs Also See for Aktor M ST L:
Table of Contents

Advertisement

„Aktor M ST L"
6.

Commissioning

6.1

Configuration of the DIP switches

f Remove the casing cover.
f Configure the DIP switches according to the valve
used (see section 12 on page 12).
Illust. 4: DIP switches
(1)
S1 ON/
OFF
(2)
S2 ON/
OFF
(3)
S3 ON/
Setting of the required stroke
OFF
behaviour in accordance with
the characteristic lines of the
(4)
S4 ON/
valve used.
OFF
(5)
S5 ON/
OFF
(6)
S6 ON/
OFF
ON = 10 V
OFF = 0 V - 10 V
- 0 V
(7)
see Illust. 5 on page 9
Automatic flushing function and valve an-
ti-blocking function
(8)
ON
activated
OFF
deactivated
Illust. 5: Characteristic line inversion DIP switch 7
101272584-V01.11.2019
8
7
6
5
4
3
2
1
ON
OFF
6.2

Connection of the power supply

f Connect the power supply according to the desired
assignment in Illust. 6 on page 9 to Illust. 8 on
page 10.
6.2.1

Steady control

1
BU
Illust. 6: Pin assignment for steady control
(1)
0 V AC/DC
(2)
24 V AC/DC
(3)
Control 0 - 10 V DC
6.2.2

3 point control

1
BU
Illust. 7: Pin assignment for 3 point control
(1)
0 V AC/DC
(2)
0 V or 24 V AC/DC
(3)
0 V or 24V AC/DC
If the DIP switch 7 is set to OFF, the stroke
behaviour will be as follows. (If the DIP
switch 7 is set to ON, the stroke behaviour
will be reversed!)
- The actuator will move to the upper lift po-
sition (see position (1) in Illust. 10 on page
10) when 24 V are applied to position/
contact (3).
- The actuator will move to the lower lift
position when 24 V are applied to position/
contact (2).
Commissioning
2 3
BN
GY
Y = 0..10 V DC
24 V AC/DC
0 V AC/DC
blue (BU)
brown (BN)
grey (GY)
2 3
BN
GY
24 V AC/DC
0 V AC/DC
blue (BU)
brown (BN)
grey (GY)
9