SUN2000-(60KTL, 65KTL)-M0
User Manual (Mexico Edition)
No.
Parameter
7
PV module type
8
String
connection
mode
Issue 06 (2020-10-12)
Description
This parameter is used to set
different types of PV modules
and the shutdown time of
the concentration PV
modules. If the concentration
PV modules are shaded, the
power drops drastically to 0
and the SUN2000 shuts
down. The energy yield
would be affected since it
takes too long for the power
to resume and SUN2000 to
restart. The parameter does
not need to be set for
crystalline silicon and filmy
PV modules.
Specifies the connection
mode of PV strings.
● When the PV strings
connect to the inverter
separately (fully separate
connection), there is no
need to set this parameter.
The inverter can
automatically detect the
connection mode of the
PV strings.
● When the PV strings
connect to one another in
parallel outside the
inverter and then connect
to the inverter
independently (fully
parallel connection), set
this parameter to All PV
strings connected.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Remarks
N/A
● If PV module type is set
to Crystalline silicon or
Film, the SUN2000
automatically detects
the power of PV
modules when they are
shaded and shuts down
if the power is too low.
● When the concentration
PV modules are used:
– If PV module type is
set to CPV 1, the
inverter can quickly
restart in 60 minutes
when the input
power of PV modules
drops drastically due
to shading.
– If PV module type is
set to CPV 2, the
inverter can quickly
restart in 10 minutes
when the input
power of PV modules
drops drastically due
to shading.
N/A
N/A