User Manual (Mexico Edition)
Alarm
Alarm Name
ID
2035
Grid Voltage
Imbalance
2036
Grid
Overfrequency
Issue 06 (2020-10-12)
Alarm
Cause
Severity
Major
Cause ID = 1
The difference between
grid phase voltages
exceeds the upper
threshold.
Major
Cause ID = 1
Power grid exception: The
actual grid frequency is
higher than the
requirement of the local
power grid standard.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Measures
1. Check that the grid
voltage is within the
normal range.
2. Check the connection
of the AC output
power cable. If the
cable connection is
proper but the alarm
occurs frequently and
affects the power
production of the PV
plant, contact the
local power operator.
1. If the alarm occurs
accidentally, the
power grid may be
abnormal temporarily.
The SUN2000
automatically recovers
after detecting that
the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the grid
frequency is within
the acceptable range.
If no, contact the local
power operator. If yes,
modify the power grid
overfrequency
protection threshold
with the consent of
the local power
operator.
100