Huawei SUN2000-60KTL-M0 User Manual page 58

Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-(60KTL, 65KTL)-M0
User Manual (Mexico Edition)
MBUS (PLC) Communication
The MBUS (PLC) communication board loads communication signals onto power
cables for transmission.
Selecting a Communication Mode
The RS485 and MBUS (PLC) communication modes are mutually exclusive.
Issue 06 (2020-10-12)
Figure 5-19 Communication mode for a single SUN2000
Figure 5-20
shows the communication mode for multiple SUN2000s.
If multiple SUN2000s are used, connect all the SUN2000s in daisy chain mode
over an RS485 communications cable.
Figure 5-20 Communication mode for multiple SUN2000s
NO TE
● The RS485 communication distance between the SUN2000 at the end of the daisy
chain and the SmartLogger cannot exceed 1000 meters.
● If multiple SUN2000s need to communicate with one another and are connected
to a PC over the SmartLogger1000, a maximum of three daisy chains can be
configured.
● If multiple SUN2000s need to communicate with one another and are connected
to a PC over the SmartLogger2000, a maximum of six daisy chains can be
configured.
● To ensure the system response speed, it is recommended that the number of
devices on each daisy chain be less than 30.
NO TE
The built-in MBUS (PLC) module in the SUN2000 does not need to be connected with
additional cables.
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-65ktl-m0

Table of Contents