Sealing The Connection Area; Starting Up The Inverter - Kaco Powador 3200 Operating Instructions Manual

Hide thumbs Also See for Powador 3200:
Table of Contents

Advertisement

Installing the inverter
Authorised electrician
7.5

Sealing the connection area

1.
The requirements of protection rating IP54 are met by closing the unused cable fittings with blind caps.
2. Put on the lid for the connection area.
3. Close and lock the housing door.
»
The inverter has been mounted and installed.
»
Start up the inverter.
7.6

Starting up the inverter

DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may start up the inverter.
Attachment of safety label in accordance with UTE C 15-712-1
FR
The code of practice UTE C 15-712-1 requires that, upon connec-
tion to the French low-voltage distribution network, a safety
sticker showing a warning to isolate both power sources when
working on the device must be attached to each inverter.
" Attach the provided safety sticker visibly to the outside of
the inverter housing.
7.6.1
Switching on the inverter
↻ The inverter has been mounted and electrically installed.
↻ The cover for the connection area is grounded and closed.
↻ The PV generator is supplying a voltage > 350 V.
1.
Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using the DC isolator switch (0 → 1).
»
The inverter begins to operate.
»
During the initial start-up: Follow the instructions of the New Connection Wizard.
Operating Instructions for Powador 3200-6600_EN
ATTENTION
Isoler les deux sources
Présence de deux
avant toute intervention
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
EN
Page 29