Maintenance/Troubleshooting
Authorised electrician
Fault
Cause of fault
Additional devices
The potential-free
that are connected
contact connects
via the poten-
to indicate an
tial-free contact
error.
suddenly start up,
even though the
"priwatt" function is
deactivated and the
inverter indicates an
error.
Table 6:
Troubleshooting
9.5

Messages on the display and the "Fault" LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are
defined in standards, e. g. VDE0126-1-1. The inverter shuts down if the values exceed or fall below the approved levels.
9.5.1
Display of status and fault messages
Display
Fault LED (red)
FS (fault status)
OS (operating
status)
Details regarding the fault or operating status can be found either on the display or in the data that was recorded
through the RS485 interface.
9.5.2
Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs. For
the status, consult the data that is logged via the RS485 interface.
OS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.
Status
Display
OS 1
Waiting for
feed-in
OS 2
Generator volt-
age
too low
OS 3
Table 7:
Operating status and fault messages on the display
Operating Instructions for Powador 3200-6600_EN
Explanation/remedy
If the "priwatt" function is not activated, the potential-free
contact functions as a fault signal relay and therefore indi-
cates errors. However, if additional devices that are provided
for the "priwatt" function are connected to the inverter via the
contact, they can still start up when the inverter experiences
an error, because the contact is connected at that point in
time. If you deactivate the "priwatt" function, we recommend
that you disconnect devices from the inverter that were con-
nected for this function.
Fault signal relay has switched.
!
ON
Feed-in was ended due to a fault.
The fault signal relay releases again.
!
OFF
The inverter feeds back into the grid again after a coun-
try-specific time period.
Explanation
!
Self-test: The grid parameters and gen-
erator voltage are being checked.
Insufficient generator voltage and
power,
status before the transition to night
shutdown
Constant volt. control
When feed-in begins, a constant gener-
ator voltage is fed in (80% of the meas-
ured open circuit voltage) for a short
period
By
Action
By
-
-
-
-